Tetra
EdgeStrip HO
®
Troubleshooting
Symptom
Row of modules does not light
Sign does not light
Individual modules do not light
Modules are dim
Maximum Loading per Tetra
Note: Load shall not
SKU
Rating
GEBIH71-2
24VDC,
GEBIH50-2
5.40W
GEBIH41-2
per module
GEBIH32-2
Maximum Remote Mounting Distance
20W Power Supply
80W Power Supply
100W Power Supply
180W Power Supply
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
This Class [A] RFLD complies with the Canadian standard ICES-005. Ce DEFR de la classe [A] est conforme à la NMB-005 du Canada.
If you have any questions about these instructions or your specific application, please contact support at [email protected].
This product is intended solely for the use of non-residential signage lighting and is not intended for use in any other applications.
Solution
• Check wire connections to power supply to ensure red stripe-to-red and white-to-black or blue connections.
• Check row-to-row polarity connections.
• Check input and output voltage and check power supply input/output connections.
• Check polarity connections.
• Remove module and replace with another working module.
• Ensure the overall length of the Tetra
• Ensure the length and gauge of the supply wire is equal to or below the recommended remote
mounting distance.
24 VDC Power Supply
®
25W
80W
Power Supply
Dimming Power Supply
Note: Load shall not
exceed 0.83A
exceed 3.3A
4 modules/
14 modules/
4ft.(1.22 m)
14 ft. (4.27 m)
18 AWG/0.82 mm
16 AWG/1.31 mm
2
Supply Wire
120 ft./36.6 m
20 ft./6.1 m
20 ft./6.1 m
20 ft./6.1 m
For the latest install guides for your product go to: www. LED.com
Conforms to the following standards:
IP66 rated: separate enclosure required for outdoor use, UL damp location rated
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are design or typical values when measured under laboratory conditions.
SIGN097 (Rev 02/12/21) GE2027-2822
LED system does not exceed the maximum load.
®
100W
Power Supply
Note: Load shall not
exceed 4.0A
17 modules/
18 ft. (5.49 m)
14 AWG/2.08 mm
2
Supply Wire
Supply Wire
–
25 ft./7.6 m
35 ft./10.6 m
25 ft./7.6 m
35 ft./10.6 m
25 ft./7.6 m
35 ft./10.6 m
III
Installation Guide
180W
300W
Power Supply
Power Supply
Note: Load shall not
Note: Load shall not
exceed 3.8A per each
exceed 4.0A per each
(of 2) output channels
(of 3) output channels
16 modules/
17 modules/
16 ft. (4.88 m)
18ft. (5.49 m)
per output channel
per output channel
32 modules/
51 modules/
32 ft. (9.75 m)
54 ft. (16.46 m)
per power supply
per power supply
12 AWG/3.31 mm
2
Supply Wire
–
–
40 ft./12.1 m
40 ft./12.1 m
40 ft./12.1 m
2