Wiring
High Voltage
Black
Active/Hot
White
Neutral
Red
Switched
low Voltage
Gray
Analog Ground
Violet
0-10V Analog output (dimming)
Wiring for Dimming + On/Off
Wiring for Non-Dimming
6
Wiring for Emergency Lighting
Emergency Fixture and Regular Fixture: Wiring to Dim
while Regular Power is Available
In the wiring diagram below, the WHS100 is powered by the
Regular power circuit. While Regular power is supplied, the
WHS100 provides switched On/Off power to the Regular Fixture
and controls dimming to the Regular and the Emergency Fixture.
Loss of Regular power to the WHS100 disables dimming control,
causing the emergency fixture to operate at maximum output.
The Emergency Fixture is powered by Emergency power. Loss of
Regular power to the WHS100 disables the WHS100 dimming
control, so the Emergency Fixture operates at maximum output.
Advisory-Emergency circuit WHS-RRUX wiring
160330 document
In the diagram below, the WHS100 is powered by the Emergency
power circuit. While Regular power is supplied to the RRU the
WHS100 provides switched On/Off power to the fixture and
controls dimming.
When the RRU senses loss of Regular power, the RRU passes
Emergency power directly to the fixture and disconnects the
WHS100 switched output. Loss of Regular power to the RRU-2
disables the WHS100 dimming control, so the fixture operates
at maximum output.
3