Change the Direction of Airflow
The 2' main section of the AAO has four large
orifices and has dual start zippers on each
end. This enables the AAO to be rotated 180
degrees, changing the direction of airflow
to either down (4 & 8 o'clock) or up (10 & 2
o'clock).
Change the Volume of Airflow
Each AAO has two independent adjustment
sleeves that slide and rotate over the 2' main
section. The adjustment sleeves have both
small and medium orifices and are held in
place with hook and loop fasteners. Simply
rotate the sleeves to select small and/or
medium orifices. For large orifices, slide the sleeves off of the 2' main section onto the inactive sections.
This will expose the large orifices and will keep the sleeves readily available if you want to decrease the
airflow. Changing the number of orifices activated (0, 1, 2, 3, or 4) and/or the size of each orifice (small,
medium, or large) changes the volume of air discharged from the AAO. NOTE: 0.5" w.g. inlet static
pressure. See Chart below for Low, Medium (Factory Setting), and High CFM volumes for each diameter.
AAO Air Volume (CFM)
(per 4 orifices)
**For more detailed instructions on adjusting the AAO, see the packing slip included with the AAO.**
Laundering Instructions
• Remove system and break down into sections
• Turn soiled side out, soak in cold water for 30 minutes
• Wash cold, gentle cycle
• Rinse thoroughly (repeat cycle if water/SimpleSox still soiled)
• Drip dry or no heat tumble dry
?
If any questions arise regarding the installation of your SimpleSox
www.ductsox.com
to
4
Diameter
Low
12"
140
16"
200
20"
320
24"
380
28"
460
or contact us at 866-DuctSox (866-382-8769).
9866 Kapp Court
Ph: 866-382-8769 or 563-588-5300
Adjustment Sleeves:
Slide and Rotate Over 2' Main Section
Small Orifice
Medium Orifice
Medium
High
200
260
280
380
460
620
560
760
680
920
Factory Setting
Peosta, IA 52068
Fax: 563-588-5330
www.ductsox.com
2' Main Section
NOTE: For Low and Medium
Settings, reduce airflow volumes
in chart by 50% if orifices are on
one side only. High Setting is not
applicable for air dispersion on
one side.
System, go
TM
© 2010 DuctSox Corp.
Large Orifice
DSSSIG0810A