Installation
Safety
Mains Voltage – There are exposed electrical conductors inside this appliance. This appliance must be
installed and serviced by a competent electricical technician to the current requirements of BS7671 and
IEEE recommendations. Before servicing this appliance, normal safe isolation procedures should be
implemented.
Do not touch the PCB while energised, it carries mains voltage.
Do not touch any connection terminals while energised.
Do not attempt to service this item when wet, or in a wet or high humidity environment.
If the housing of the control panel becomes damaged, you must shut down and securely isolate this
appliance immediately.
You must connect this appliance to a grounded 3 wire supply, protected by suitable overload protection.
Connected pumps and solenoids are earthed via the control panel, and may otherwise become live.
If the power cables are damaged, either to of from the controller then shut down and isolate this appliance.
The combined loading of pumps and solenoids connected to this appliance must not exceed 20A using the
supplied mains flex. Contact the manufacturer for advice if you need to exceed this rating.
Do not attempt to repair any part of the circuit board. Refer to the manufacturer for advice.
Included Components
1 x Control Panel
4 x Level Sensors (magnetic reed switch mini-float)
1 x Wall mounting brackets
Layout
DTC200 is a wall mounted control panel designed to control 3 pumps or valves at 230VAC single phase, or
any voltage via external relays/contactors. No fluid passes through the control unit itself and it's location in
relation to other equipment is only constrained by cable distances.
The control panel cannot be mounted outside, it is splash proof but not designed to resist persistant rain or
immersion.
Connected pumps or valves mst be less than 10A@230VAC
Voltage drop will affect the cable size needed to take power to your pumps. Over very long runs, you may
find it more economical to install contactors near to the pumps, allowing you to control the pumps with a