BX308 XP Gas Detection Controller
BX308 XP 8 Sensor Gas Detection Controller
8
Sensor
Conventional
8888
Illuminated
Digital Display
4-20mA
IP65
FEATURES
■
Eight sensors
■
Datalogging Facility
■
Wall mounted
■
Illuminated digital display
■
Detection of Toxic 0-300ppm / Explosive Gas(es)
0-20%LEL
■
4-20mA signal sensor input
■
2 alarm stages - Pre-alarm and main alarm
■
IP65 protective rating
■
CE certified and approved to EN 50194 EN 50291 EMC
EN50270
■
3 years guarantee
OVERVIEW
The control unit BX308 XP has been designed and built to meet
the current requirements of the Market and in compliance with
European Standard for checking gas presence in a versatile and
innovative using conventional sensors.
Up to 8 remote sensors from 4-20mA can be connected in
conventional mode for a single area. Gas concentration measured
by each sensor is sequentially shown on display, with a location
description.
When one of the connected sensors exceeds pre-alarm or main
alarm setpoints, the control unit activates the internal audible alarm,
depending on the concentration of gas measured, and shows on the
display the number of the sensor the amount of gas measured and
its origin; the alarm triggered is saved in a memory (Datalogger).
The data stored can be printed (up to maximum 50 events). The
control unit features two levels of alarm: 1st level, pre-alarm. This
data is variable. The technician can modify pre-alarm intervention
for every sensor according to the type of plant to be controlled.
The level can be selected from 5% to 9% of L.E.L. or from 75 to 135
ppm. Main alarm is set from 10-20 % of L.E.L. or 150-300ppm. The
control unit is equipped with a main alarm relay which can be set
with or without Positive Safety Switch to enable further independent
control of a solenoid valve. Finally, the control unit allows the user to
control the actual operation of the sensors coupled.
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
SPECIFICATION
Power
Power Supply
230V (enclosure) 12VDC module
Secondary Battery
(Not supplied) 12VDC ± 10% Max 2.2Ah
Battery Charger
Charger Capacity 2.2Ah
Power Consumption
12V - 25W Maximum
230V - 30W Maximum
Relay Contact Range
10A resistive 230VAC, 5A 30VDC resistive
Alarm Settings
Pre-Alarm No.1
Can be set from 5% LEL (75ppm) to 9% LEL (135ppm)
Main Alarm
10-20% LEL / 150-300ppm
Sensor Fault
Short circuit, interruption, sensor deterioration
Technical Specification
Dimensions
Width 360mm | Height 320mm | Depth 135mm
Weight
260 grams
Display
Illuminated digital display
Mounting
Wall & Panel mounted
Input Signal
4-20mA
Device Precision
1% FS
Reaction Time
<2 seconds
Working Temperature
-10°C to 45°C
Start-up Self-Diagnostic Delay
90 seconds
Protective Rating
IP65
Configuration
Positive Safety
Yes (General functions menu)
Main Alarm Relay Actuation
Yes (General functions menu)
Gas Type Selection
Yes (Sensors menu)
Timed Sensor Test Facility
Yes
Emergency Stop Connections
Yes
O
Compatibility as Standard
Yes (Sensors menu) - Increase/Depletion
2
Perhipheral Specification
No. of Remote sensors
8 sensors
Maximum Sensor distance
100m
Cable Diameter for sensors
1mm
(Screened and earthed at the controller end)
Compatibility
Sensor Compatibility
All Duomo Sensors (Explosive, toxic gas and oxygen)
Approvals, Certifications and Guarantee
Approvals
EN 61010-1, EN 50270, EN 50271, EN 45544-3,
EN 60079-29-1, EN 50104
Guarantee
3 years as standard
1
CSA
2