BX308 XP Gas Detection Controller
Connections & Interface
f
1
2
3
1
2
3
4
a
b
Interface
1. MAINS Illuminated when BX308xp is powered by mains voltage.
2. Battery Illuminated when BX308xp is powered by battery, Flashes when battery voltage is less than 10.8 V
3. PROBE OVER LOAD Illuminates when short circuit or a high absorption of current by the sensor and the relative
connection cables. Check the battery and the connection cables.
4. BATTERY OVER LOAD Illuminated when battery is connected incorrectly or there is an abnormal current
absorption. Check the battery and the connection cables.
5. FAULT Illuminated and flashes when a connected sensor is faulty, the connection cables are interrupted, or there
is a connection error. When this LED is on, the device is no longer able to detect and activates all the relays, both
on the 1st threshold and on the 2nd threshold. To restore the operation, sensor must be repaired or removed using
the setting program and the RESET button must be pressed. This signal is type "autoreset"
6. PRE-ALARM LED (PRE-ALARM) Illuminated when the gas concentration level has reached the pre-alarm
threshold, which can be modified by the user (see
7. MAIN ALARM (GENERAL ALARM) Illuminated when the concentration level of the gas has reached the main
alarm threshold, which can be modified by the user (see
8. EXIT ALARM Illuminated when you press the remote alarm button, at the same time the word "BTN" appears on
the display
9. EXTERNAL SIREN LED for activating the EXTERNAL SIREN. Illuminates RED when external siren is
disconnected. (Access to this function requires password).
10. TEST button Pressing and holding this button simulates a gas leak.
11. RESET button Press this button to reset all memories.
12. Printer USB port Connection to print the data stored in the memory.
13. Restart button It is used to Reset the control unit without having to remove primary voltage.
14. Expansion card connection Quick-fit socket for inserting expansion cards. cod. CARD-RLS4 Relay expansion
card, cod. CARD-BMS16 conversion board from current to voltage
External manual alarm button.
The control unit is designed to be connected to a manual alarm button. Pressing the button the control unit will go
directly into alarm even when it is in the programming state or warm up, closing all the auxiliaries connected to it.
When pressed on the message "alarm activated by external button" is displayed on LCD.
t: 01905 797989
e: [email protected] | w: www.duomo.co.uk
g
4
5
6
7
8
9
1
2
3
4
5
5
6
1
2
3
4
5
6
c
d
h
10 11
13
14
Power
Pre Alarm
6
Battery
Main Alarm
7
OL Probes
Exit Alarm
8
OL Battery
Siren Status
9
Fault
10
11
12
RESET
TEST
7
8
e
Status
conditions).
Status
conditions).
6
i
Made in Italy