475 e2 Instrukcja instalacji - Strona 2
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Wentylator 475 e2. 475 e2 7 stron. With 5/uni-fr
DIMENSIONAL DIAGRAMS (All dimensions in inches (mm)
INSTALLATION POSITION
Ductless e2 ventilation devices with heat recovery can only function in pairs operation in opposite directions.
Each fan operates 70 seconds (50 seconds for e2 short) in supply air operation, the other 70 seconds (50
seconds for e2 short) in exhaust air operation at the corresponding set flow rates. After which both air flows
directions are changed. This assures that the total of supplied ventilation volume is equal to the total exhausted
volume. If a pair of fans in this balanced push-pull operation is installed in two different rooms of a dwelling, a
sufficiently dimensioned interconnection (undercut door, etc.) between the rooms should be installed to allow
unrestricted air movement between these spaces. Please see the product page at foursevenfive.com for videos.
OPERATING CONDITIONS
OPERATING CONDITIONS
Rated conditions: 5ºF to 104ºF (-15ºC to +40ºC) with relative humidity up to 65%.
During the heating period it is possible for very small amounts of condensation to form on grills if such conditions
arise. If these limitations of use are exceeded for extended periods of time, the device can be closed with the
indoor cover. Do ensure IAQ is maintained in such cases.
2
Questions? Email: [email protected] | Call: 800-995-6329