2. Prepare the following assemblies on the site.
No.
Name
1
2-core shielded cable
2
86 Electrician box
Wiring Tube(Insulating
3
Sleeve and Tightening
Screw)
4
KNX power module
5
Communicate module
Note to installation of GW-KNX(A) - (K05-KNX 01 A):
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor D1D2E ports.
2. C ircuit of GW-KNX(A) - (K05-KNX 01 A) is low voltage circuit. Never connect
it with a standard 220V/380V circuit or put it into a same Wiring Tube with the
circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. A fter finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. T he default physical address of the GW-KNX(A) - (K05-KNX 01 A) is 15.15.255,If
there are two or more KNX modules, then the physical addresses can not repeat.
The physical address can be changed by ETS software.
Qty.(embeded
Specification (only
into wall)
1
RVVP-0.5mm
1
1
1
1
4
for reference)
2
x2
Remarks
Max 350m