Quick start "Commissioning and operation"
ATICS-...-DIO Quick start
Automatic transfer switching devices for safety power supplies
Software version: D333 V1.2x/D334 V1.2x/D335 V1.0x
This reference guide does not replace the operating manual. You will find the operating manual in the download area of our homepage. Make sure
that the personnel has read this manual and understood all instructions relating to safety.

1. Safety instructions

Caution: Missing or false messages on the MK..., TM... or
FTC... because of out-dated software.
Replace or update older operating software of MK..., TM...,
FTC... or COM460
Update TMK-SET configuration software.
The attached checklist includes both the factory defaults and installation-specific settings for the ATICS® transfer switching device. Please carry
out all the work outlined in the list and log each test step.
Keep the checklist with this manual in the vicinity of the device.

2. Enabling manual mode

3. Configure MK... resp. TM...
MK... resp. TM... must display at least the following faults detected
by the ATICS®:
• Failure Line 1, failure Line 2
• Device error, device failure ATICS®
• Failure of the other MK... or TM...
• Device error with complete text or error code

4. Minimum parameter settings

The following minimum default settings have to be carried out:
• BMS bus address (see "Settings menu 8: Interface" in the oper-
ating manual)
• Delay times (see chapter "Setting and testing according to
checklist" in the operating manual)
By default, there is no password set on the ATICS®.
For operation of the device, it is absolutely essential to enter
and enable a password (see "Settings menu 10: password" in
the operating manual).
ATICS-DIO_D00080_02_Q_XXEN/04.2017
Open the transparent
cover of the automatic
transfer switching device.
The display shows "Man-
ual mode".
Note: Configure MK... resp. TM... in a meaningful way.
In addition to the message, configure a short remark of what
needs to be done and who is to be informed.

5. Operator control and display elements

1
2
3
4
1
2
ALARM COM
Pos.
LED/Button
Meaning
1
LC graphical dis-
play
2
LED "1"
lights up when Line 1 is ready
3
LED "2"
lights up when Line 2 is ready
4
LED "ALARM"
lights up when there is an alarm
message
5
LED "COM"
flashes during communication via the
BMS bus
6
"INFO" button
to query standard information,
"ESC" button
to leave the menu function without
changing parameters
7
"TEST" button,
Calls up test menu
Up button
Parameter changes, scrolling
8
"RESET" button
Resets alarm and fault messages,
unlocks switching back interlocking
function
Down button
Parameter changes, scrolling
9
"MENU" button
Toggles between the standard display,
alarm display and the "MENU"
Enter button
Confirms parameter changes
5
6
7
8
9
1