Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
(See note 5 for RF
zones)
Response when system disarmed and zone is:
Intact EOL
Open
RF zone normal
RF zone N/A
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 1 = EOL + Open
ENTRY 3
(See note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
Open
RF zone normal
RF zone N/A
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 3 = EOL + Open
ENTRY 5
(See note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
Open
RF zone normal
RF zone N/A
0 = normal
0 = normal
1 = alarm
4 = alarm
2 = trouble
8 = trouble
3 = fault
12 = fault
Entry 5 = EOL + Open
ENTRY 7
Display Faults
Power Reset/
Verification
0 = show alarms
0 = no
when armed
4 = power reset
& disarmed
after fault
1 = don't show
(by code + OFF)
12 = verification
alarms when
(see zone
armed
(show
type 16)
alarms, trbles,
faults when
disarmed)
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
ENTRY 9
Alarm Sounds
Use Bell
Timeout
0 = none
0 = no
1 = steady
4 = yes
keypad
2 = steady bell
see fields *32,
and keypad
*33
3 = pulsing bell
and keypad
Entry 9 = alarm sounds + bell timeout + fire zone
ENTRY 2
(See note 5 for RF zones)
Auto
Restore
Shorted
RF zn off-normal
0 = normal
0 = no
1 = alarm
4 = yes
2 = trouble
3 = fault
Entry 2 = Short + auto restore + vent zone
ENTRY 4
(See note 5 for RF zones)
Byp. when
disarmed
Shorted
RF zn off-normal
0 = normal
0 = no
1 = alarm
4 = yes
2 = trouble
3 = fault
Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 6
(See note 5 for RF zones)
Dial Delay
(see field *50)
Shorted
RF zn off-normal
0 = normal
0 = no
1 = alarm
4 = use delay
2 = trouble
3 = fault
Entry 6 = Short + dial delay + fault delay
ENTRY 8
Use Entry
Use Exit
Delay 1/2
Delay
0 = no
0 = no
1 = delay 1
4 = use exit
2 = delay 2
delay
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
ENTRY 10
Respond as
Trouble
Fire Zone
Sounds
0 = no
0 = none
8 = yes
1 = periodic
beep
see zone type
2 = trouble
09; see note 4
beeps
Entry 10 = trouble sounds + chime
Entry Zone Type 90
Vent Zone
1
2
0 = no
3
8 = yes
4
5
6
7
8
Byp. when
9
armed
10
0 = no
To calculate the value for each entry:
8 = yes
Simply add the values of the selected options
in each of the entry's columns (one option per
column). For example, to program Entry 2 for
"alarm response to short," "auto restore on,"
but not a "vent zone," enter 5 ("1" for alarm
short + "4" for auto restore yes + "0" for vent
Fault Delay
zone no).
(see field *87)
0 = no
8 = use delay
see note 1
Respond as
Interior Type
NOTES:
0 = no
1. Do not use the "fault delay" option with a
8 = yes
see note 2
2. To create an interior type zone, select
3. Do not set fire zones to respond as a
4. 4219/4229 modules must use EOLRs or
Chime when
Chime Mode On
5. RF Zones: The "open" option in entries 1,
0 = no
4 = yes
– 8 –
Entries for Fields *182 and *184
Zone Type 91
(field *182)
(field *184)
INTACT
OPEN
SHORTED
EOL
ZONE-003-V0
Zone Conditions Represented
in Entries 1-6
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
"respond as interior zone type" (entry 8,
interior type = yes), and set zone
response to "fault" in entries 3-4 to ensure
fault displays; do not set as "normal,"
"alarm," or "trouble."
"fault" (entries 1-6), otherwise faults will
not display unless the [∗] key is pressed.
unpredictable results may occur.
3, and 5 is not applicable for RF zones.
Use the "intact EOL" option for normal RF
zone conditions and "shorted" for off-
normal RF zone conditions.