ZN551 Control Module • Rev. 3/17/2005
LStat
Rnet
LStat
IN-4
IN-1
Thermistor/dry contact
0-5Vdc
IN-2
Thermistor/dry contact
0-5Vdc
Connect the digital output wiring to the screw terminals on the ZN551
6
and to the controlled device.
Motor
Any DO
Any DO
24 Vac or
Bus
24 Vdc
7
Connect the analog output wiring to the screw terminals on the ZN551
and to the controlled device.
Gnd
Motor
Any AO
+
Gnd
Valve
Any AO
+
NOTE Current from the analog outputs can drive a 20 mA device. To use
an analog output for this purpose, you may need to add a 1/2 watt
resistor in series with the device to achieve the required total resistance
of 500 Ohms. For example, to drive a device that has 100 Ohms of
resistance, wire a 400 Ohm resistor in series with the 20 mA device to
achieve 500 Ohms resistance.
8
Insert the power screw terminal connector into the ZN551's power
terminals.
8
0-10 V
0-10 V