Automated Logic ZN551 Instrukcje techniczne - Strona 16
Przeglądaj online lub pobierz pdf Instrukcje techniczne dla Router sieciowy Automated Logic ZN551. Automated Logic ZN551 18 stron. Control module
To communicate through the local access port
To set up a Local
Access connection in
WebCTRL
Troubleshooting
ZN551 Control Module • Rev. 3/17/2005
Using a computer and an APT, you can communicate locally with the ZN551
to download memory or to troubleshoot.
PREREQUISITES
•
A computer with an RS232 port
•
An APT with cables. See the APT Technical Instructions
(http://info.automatedlogic.com).
Connect the computer to the APT, and then the APT to the control
1
module.
2
Set the APT's Mode Select switch to 485.
Set the APT's Exec. 4 Relay switch to Network.
3
On the CFG tree, select Connections.
1
2
On the Configure tab, click Add.
From the Type drop-down list, select BACnet Local Access.
3
4
Optional: Edit the Description.
Type the computer's Port number where your APT is connected.
5
Set the Baud rate to 115200.
6
7
Click Accept.
On the View tab, click the drop-down arrow next to your device's
8
network Connection, then select BACnet Local Access.
9
Click Accept.
10 On the Configure tab, select BACnet Local Access, then click Start.
If you have problems mounting, wiring, or addressing the ZN551, contact
ALC Technical Support.
16
9-pin
APT cable
© 2005 Automated Logic Corporation
Connect to the
control module's
Local Access port
Rnet
adapter
cable
8-pin
APT cable