To communicate through the local access port
To set up a Local
Access connection in
WebCTRL
Troubleshooting
ZN551 Control Module • Rev. 3/17/2005
Using a computer and an APT, you can communicate locally with the ZN551
to download memory or to troubleshoot.
PREREQUISITES
•
A computer with an RS232 port
•
An APT with cables. See the APT Technical Instructions
(http://info.automatedlogic.com).
Connect the computer to the APT, and then the APT to the control
1
module.
2
Set the APT's Mode Select switch to 485.
Set the APT's Exec. 4 Relay switch to Network.
3
On the CFG tree, select Connections.
1
2
On the Configure tab, click Add.
From the Type drop-down list, select BACnet Local Access.
3
4
Optional: Edit the Description.
Type the computer's Port number where your APT is connected.
5
Set the Baud rate to 115200.
6
7
Click Accept.
On the View tab, click the drop-down arrow next to your device's
8
network Connection, then select BACnet Local Access.
9
Click Accept.
10 On the Configure tab, select BACnet Local Access, then click Start.
If you have problems mounting, wiring, or addressing the ZN551, contact
ALC Technical Support.