c. Flexible conduit entry mounting
For conduit entry, mount the backplate to the wall. Break out the conduit hole
on the housing (see fig. 3b). Assemble the conduit to the backplate.
d. Line cord installation (option)
Mount the backplate to the wall.
7. Make the proper connections. The system can accept input voltages of 120/
277 VAC (see fig. 4).
120 VAC — Connect the black (120 VAC) and white (neutral) leads to the
building utility. Insulate the unused wire.
120 VAC with line cord (optional) — Make the proper connections. Connect
the wire with the smooth side from the line cord to the black (120 VAC) on the
unit and the ridged wire from the line cord to the white (neutral) on the unit.
Insulate the unused wire. Connect the green wire on the transformer (if appli-
cable) or insulate the unused green wire from the line cord.
277 VAC — Connect the orange (277 VAC) and white (neutral) leads to the
building utility. Insulate the black wire.
Route entry wires to avoid contact with the transformer,
IMPORTANT:
battery terminals and charger PCBA. Refer to figure 4.
8. Connecting external lamps: pass external DC wires into the unit and connect
to internal lamp wires or directly to the PCBA depending on the model.
9. When ready to energize AC circuit, connect the battery.
10. Slide the housing over the tabs; conduit side on housing over conduit side on
backplate (see fig. 5). Assemble the conduit side first, then align the tabs on
the other side of the housing and of the backplate. Press together until it
snaps.
11. Remove the clear lens by prying with a screwdriver, where indicated (see fig.
2).
12. Rotate heads to desired position and replace clear lens.
13. Energize AC. The AC pilot indicator, located under the cover, will illuminate
(see fig. 5).
Vandal resistant (option)
Units with vandal resistant option: there are three vandal resistant screws. Two are
securing the cover, and the other one secures the housing and the backplate (see
fig. 6).
Unit testing
Manual testing
Press test switch (see fig. 5). The emergency lamps will illuminate. When switch is
released, lamps will go off. Allow unit to charge for 24 hours before initial testing.
Automatic testing and diagnostics
The automatic testing and diagnostic function includes a micro-controller which
self-tests the unit on a monthly basis and identifies as well displays failures of the
electrical components: battery, battery charger, lamps.
Self-test
The self-test is performed every month for 1 minute, every 6 months for
30 minutes, and annually for 90 minutes.
Diagnostic function
–For diagnostic function, refer to "User Manual for AD"
–For Nexus models, refer to "Nexus addendum"
Maintenance
None required.
If AC supply to the unit is to be disconnected for 2 months or more, the battery
must be disconnected.
Warranty: For the complete warranty information, please refer to the landing
page of our website (http://www.emergi-lite.com/usa/).
Emergi-Lite®
Tel: (888) 552-6467
®
Fax: (800) 316-4515
Provider Series - Emergency lighting
DC wires
Conduit hole
to knock out
Figure 3d
All AC or DC connections must be
IMPORTANT:
done in individual external junction
boxes.
Black 120 VAC
Orange 277 VAC
White neutral
Make all AC connections
on this side of battery
Battery
Figure 4
Unused primary wire must be insulated to prevent shorting.
Close housing until it snaps
Assemble conduit
side first
Figure 5
Vandal resistant
screws for
vandal resistant
option
Figure 6
www.emergi-lite.com
AC wires
Transformer
Housing
PCB
AC pilot indicator
Test switch
09/16 750.1705 Rev. E
2/2