DIP SWITCH 4: Configures the system for either 50Hz or 60Hz. The switch should be in the
ON position or UP, for a 60Hz system. The switch should be in the OFF position, or DOWN for
a 50Hz system.
DIP SWITCH 5: This switch should be left in the OFF position or DOWN for the ES53.
Switch 5 configures proper filtering for AC generator sensing.
DIP SWITCH 6: DIP switch 6 enables and disables the Time Delay Normal to Emergency
(TDNE) feature. To enable the TDNE function, the DIP switch should be in the ON or UP
position. To disable the TDNE function, the DIP switch should be in the OFF or DOWN
position.
DIP SWITCH 7: DIP switch 7 enables the Time Delay Engine Start (TDES/Preheat). To enable
the TDES/Preheat function, the DIP switch should be in the ON or UP position. To disable the
TDES/Preheat function, the DIP switch should be in the OFF or DOWN position.
DIP SWITCH 8: DIP switch 8 enables the Time Delay Engine Cooldown (TDEC) and the Time
Delay Emergency to Normal (TDEN). To enable the TDEC and TDEN function, the DIP switch
should be in the ON or UP position. To disable the TDEC and TDEN function, the DIP switch
should be in the OFF or DOWN position.
DIP SWITCH 9: Not Used
The following timers are included as standard in the ES53, one of which is adjustable. Special
time settings are available from the factory.
1: TDES: Time Delay Engine Start: Adjustable from 0 to 32 Seconds. This delay is necessary to
prevent unnecessary engine starts. This delay also doubles as a preheat timer by utilizing
terminal number 12 for diesel glow-plugs, if necessary.
2: TDNE: Time Delay, Normal to Emergency: 4 seconds & 55 Hz. This allows the engine to
stabilize before load transfer. This delay waits 4 seconds and then proceeds to very the engine
has reached a frequency of 55Hz before transferring.
3: TDEN: Time Delay, Emergency to Normal: 3 minutes. This allows a delay after the utility
returns, to insure it has indeed returned and stabilized.
4: TDEC: Time Delay, Engine Cool: 5 minutes. This allows the engine to continue running for
a set time after re-transfer of load to the utility, to circulate coolant for a safe cool-down.
Installation and User Manual for the ES53 Control Module
TIMER FUNCTIONS
15