ADEMCO 5808 Instrukcje instalacji
Przeglądaj online lub pobierz pdf Instrukcje instalacji dla Alarm dymowy ADEMCO 5808. ADEMCO 5808 4 stron. Photoelectronic smoke/heat detector with built-in wireless transmitter
Również dla ADEMCO 5808: Instrukcje instalacji (5 strony)
5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
5808 Photoelectronic Smoke/Heat Detector with
Built-in
Built-in
Built-in
Built-in Wireless
Built-in
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONS
Power Source:
Maintenance Limits (Maintenance signal
is activated at either smoke level):
Height:
Diameter:
Weight:
Operating Ambient Temperature Range:
Operating Humidity Range:
Heat Sensor:
Agency Listings:
Before installing detectors, please thoroughly read these installation instruc-
tions and Manual I56-407, Guide for Proper Use of System Smoke Detectors,
which provides detailed information on detector spacing, placement, zoning,
wiring, and special applications. Copies of this manual are available from
ADEMCO.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following
NFPA 72 requirements. The detector should be cleaned at least once a year.
WARNING: Do not use the maintenance signal as an indication that the
detector has reached the limits of its nominal sensitivity range. Maintenance
only indicates that the detector may need cleaning or can no longer respond
to smoke and shall not be used as a sensitivity indicating means.
GENERAL DESCRIPTION
The 5808 photoelectronic smoke/heat detector with built-in wireless transmit-
ter is intended for use with wireless alarm systems that support QED 5800
series devices. Refer to QED control communicator installation instructions
for compatibility. The 5808 smoke/heat detector can be used with 5881 series
(L, M, H) and 5881EH receivers for residential installations. The 5808 smoke/
heat detector can be used with the 5881EH receiver for commercial installa-
tions. The transmitter can send alarm, tamper, maintenance (when QED
control panels are equipped to process maintenance signals), and battery
condition messages to the QED system's receiver. The maintenance signal
will either indicate that the photo chamber requires cleaning or that the detector
can no longer respond to smoke and may need replacement. Refer to the
wireless system's instructions for the maximum number of transmitters that can
be supported.
The 5808 sounds its built-in horn when smoke reaches the detector (the
LED also flashes rapidly) or when the air temperature reaches 135° F (the
LED flashes normally, about once every 40 seconds). A message is also
sent to the wireless QED control panel and the smoke detector's ID number
is displayed at the console. The alarm message is transmitted every 4
seconds until the smoke condition has cleared and the detector has reset.
About 1 second after the horn stops, a RESTORE message is transmitted
to the QED control panel and the ID number can be cleared from the panel.
During normal, maintenance, and low battery conditions, the LED flashes
approximately once every 40 seconds.
BATTERY INSTALLATION AND REPLACEMENT
The 5808 is powered by two 3-volt CR123A or DL123A Lithium batteries
(included). The detector checks for low batteries at every normal LED flash.
If a low battery is detected, the transmitter sends a low battery message to
the QED control panel, which beeps and displays the detector's ID. This
condition will exist for a minimum of seven days, and then the detector's
horn will "chirp" about every 40 seconds. The batteries should be replaced
BEFORE the chirps begin. BE SURE TO REPLACE BOTH BATTERIES
WITH FRESH ONES.
AD300-00-00
fi
R
For use with QED control panel ONLY!
Wireless
Wireless T T T T T ransmitter Installation Instructions
Wireless
ransmitter Installation Instructions
ransmitter Installation Instructions
Wireless
ransmitter Installation Instructions
ransmitter Installation Instructions
Two 3-volt CR123A Lithium Batteries (included). (Replace with Duracell DL123A, Sanyo
CR123A, Panasonic CR123A, ADEMCO 466, or Varta CR123A.)
Hot Sensitivity: 0.65% ± 0.15% per foot
Cold Sensitivity: less than 6% per foot
2.5 inches (14 cm)
5.5 inches (64 mm)
0.7 lb. (310 g)
4.4° to 37.8° C (40° to 100° F)
5% to 95% Relative Humidity
135° F Fixed Temperature Electronic Thermistors
UL 217; UL 268 – Residential, Commercial Installations
To replace batteries:
1.
Remove the detector from its mounting plate by twisting the detector counter-
clockwise. Remove batteries, if replacing, and dispose properly.
2.
Install two new 3-volt CR123A Lithium batteries in the battery compart-
ment. Follow the polarity diagram inside the compartment.
3. Reinstall the smoke detector onto the mounting plate by turning the
detector clockwise.
4. Test the detector as described in the TESTING TRANSMITTER SIG-
NAL section of this manual. The LED should flash about once every 40
seconds to indicate normal operation. If the batteries are not installed
correctly, the smoke detector will not operate and the batteries may be
damaged. If the detector does not appear to be sending a signal during
any of the tests, check for correct battery installation.
Indicator Light
Pulsing: Normal/Thermal Alarm
Fast Blink: Smoke Alarm
None: Call for Service
Test Module
Port
Figure 1. 5808 Wireless Smoke/ Heat Detector
PROGRAMMING
The smoke detector's ID must be enrolled in the QED control panel during
installation of the system. The QED control panel should be programmed
to enroll the 5808 as an "RF" unit (must be programmed as "supervised RF"
for UL installations).
Put the QED control panel in the program
ming mode and perform the following:
With the QED control panel, program the detector as loop 1 and either
manually enter the serial number that is on the label of the 5808, or press
the test switch to cause a transmission. Additional transmissions will cause
the "Confirm" display to appear on the keypad display.
See the QED control unit's installation instructions for further details.
ADEMCO, 165 Eileen Way, Syosset, New York 11791
Previous Menu
Test Switch
A78-2332-01
I56-918-06