AGS Parksafe Control Panel Instrukcja instalacji i obsługi - Strona 10

Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Panel sterowania AGS Parksafe Control Panel. AGS Parksafe Control Panel 16 stron. Ventilation control panel
Również dla AGS Parksafe Control Panel: Instrukcja instalacji i obsługi (16 strony), Instalacja, obsługa i konserwacja (16 strony), Instrukcja instalacji, obsługi i konserwacji (20 strony)

AGS Parksafe Control Panel Instrukcja instalacji i obsługi
Installation & Operation Manual

Quick Tips

CONNECTION
The best way to connect devices in a MODBUS RTU is a 'DAISY CHAIN' method.
MAXIMUM DISTANCE
You may encounter problems when powering gas sensors beyond 500 yards from one control
panel, in this instance, contact your supplier.
TERMINAL RESISTANCE
Signal communication issues may occur. To avoid this, terminating at each end of a chain may
help the quality of the data signal by turning on the 120ohm terminal resistor switches.
GROUNDING
If you are encountering noise or irregular or abnormal problems with a Modbus link, the problem is
likely related to grounding, incorrect shielding or wiring main power next to Modbus wiring.
CABLES TO USE
A shielded and twisted pair cable is used. The shielding can be of 2 types: braided [like a mesh of
thin conducting wires] or like a foil [consisting of a thin sheet of metal covering the twisted wires].
PROTECTION
High concentrations of alcohol found in many products may damage, deteriorate or affect the gas
sensing elements of Detectors – such as; wine; deodorants; stain removers; thinners etc.
IDENTIFICATION
Remember to individually ID each connected detector by configuring the ID switches on the circuit
board. Make a plan, map and/or note of the location of all connected detectors for tracing and
locality purposes.

Specification

Operating Temperature / RH Approx.
Gas Detector Wiring Length Approx.
O/All Dimensions (H x W x D) mm / inch
AGS Parksafe Panel - IOM Iss: 6 10-20
Product
Display
Power Input Voltage
Current Consumption Approx.
Internal Fuse
Audible Alarm Buzzer dB
Maximum Gas Detectors
Wire ratings:
Housing Material
Flame Rating
Approvals
AGS Parksafe Ventilation Control Panel
4.3" Touch Screen TFT
100-120V AC
48W max (fully loaded)
3.15A
14 – 122°F / 30-85% RH non-condensing
65 dB (300mm distance in quiet conditions)
16 max
± 500 Yards
18AWG min
Polylac PA-765
UL 94
CE, RoHS
7.08 x 10 x 3.03"
Parksafe