UNIT MOUNTING
Table 4.1 - Maximum Mounting Heights
Horizontal Type
Height (ft)
Model No.
Std. L.O.T.
WTC/WSC 18
8
9
WTC/WSC 24
9
11
WTC/WSC 33
10
12
WTC/WSC 47
12
14
WTC/WSC 63
14
16
WTC/WSC 86
15
17
WTC/WSC 108
17
19
WTC/WSC 121
16
18
WTC/WSC 165
19
21
WTC/WSC 193
18
—
WTC/WSC 258
19
22
WTC/WSC 290
20
23
WTC/WSC 340
20
23
—
—
—
—
—
—
➀ With horizontal louvers opened 30° from the vertical plane. WTC units have top and bottom piping connections, WSC units have side connections. All have copper tubes.
➁ V and PT models have copper tubes, VN and PTN models have cupronickel tubes. Mounting heights are maximum for heaters operating at standard conditions
(2 lbs. steam or 220°F water with 60°F entering air). Heights listed for Louver or Cone-Jet are with deflectors in fully-opened position. Refer to Figure 4.2 for correction of
mounting heights under other operating conditions. Maximum mounting height will be reduced as entering air temperatures exceed 60°F.
Figure 4.2 - Maximum Mounting Heights Correction Factors
1.3
1.2
1.1
1.0
.9
.8
.7
.6
.5
150
160
170
180
These correction factors are to be used as multipliers to correct the maximum recommended mounting heights of unit heaters when operated with steam pressures other
than 2 pounds or with water at other than average temperature of 220°F.
Figure 4.3 - Horizontal Unit Delivery
H
Figure 4.3 Vertical Cone Jet
H
4
"Power-Throw" Type
Height (ft)
Model No.
Std. L.O.T.
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
WPC/WPN 279
16
WPC/WPN 333
17
WPC/WPN 385
17
WPC/WPN 500
18
WPC/WPN 610
20
WPC 952
21
2
5
190
200
210
220
230
Figure 4.6 - Vertical Truncone
H
No Deflector
Height (ft)
Model No.
Std.
—
WVC/WVN 42
11
—
WVC/WVN 59
14
—
WVC/WVN 78
15
—
WVC/WVN 95
15
—
WVC/WVN 139
18
—
WVC/WVN 161
20
—
WVC/WVN 193
22
—
WVC/WVN 212
22
—
WVC/WVN 247
26
—
WVC/WVN 279
30
—
WVC/WVN 333
30
—
WVC/WVN 385
30
—
WVC/WVN 500
37
22
WVC/WVN 610
36
—
WVC 952
37
Steam Pressure
10
20
30
240
250
260
270
280
Average Water Temp – F
Figure 4.4 - Vertical One-Way & Two-Way Louvers
H
AIR 1-550.30
Vertical Type with Deflectors
Cone-Jet
Truncone
Height (ft)
Height (ft)
L.O.T.
Std.
L.O.T.
Std.
13
15
17
8
16
19
22
9
19
20
26
11
19
20
26
11
23
24
31
13
26
27
35
14
27
30
36
16
27
30
36
16
32
34
42
17
36
37
45
18
36
37
45
17
36
36
43
17
45
44
54
19
44
43
52
19
45
—
—
—
50
70
100
290
300
310
320
330
H
Louvers
Height (ft)
L.O.T.
Std.
L.O.T.
9
13
15
11
16
18
14
17
22
14
17
22
17
21
26
18
23
30
19
25
31
19
25
31
21
30
37
22
35
41
20
35
41
20
35
41
24
42
51
24
41
50
—
—
—
150
340
350
360
370
H