Fujitsu ETERNUS AF250 Podręcznik planowania witryny - Strona 28
Przeglądaj online lub pobierz pdf Podręcznik planowania witryny dla Przechowywanie Fujitsu ETERNUS AF250. Fujitsu ETERNUS AF250 38 stron. Hybrid storage systems, all-flash arrays, power synchronized unit
Również dla Fujitsu ETERNUS AF250: Instrukcja konfiguracji (12 strony), Podręcznik konfiguracji (18 strony), Środki ostrożności (12 strony)
1.
ETERNUS AF Installation
Outlet/Socket Specifications
●
For Direct (No Power Distribution Unit) Connections
The following diagram shows a power supply connection example when no power distribution units are used.
Figure 11 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used
CP
PSU:
Power Supply Unit
CP:
Circuit Protector
Input Power Supply Lines
Multiple power supply facilities in the building or multiple UPS units are recommended for power supply redun-
dancy. A redundant configuration is used for the power supply of the ETERNUS AF. Business can continue even if
one of the power supply lines fails.
However, a single power supply facility configuration is also allowed for the entire system optimization (includ-
ing the server). When selecting a single configuration, take into consideration the availability of the system.
Figure 12 Dual-Line Power Supply (When Connecting to Power Sockets)
Line 1
Line 0
ETERNUS AF
Drive enclosure
Controller
enclosure
Line 0
•
Only connect the ETERNUS AF to circuit protectors.
Power distribution unit
ETERNUS AF
PSU
PSU
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Site Planning Guide
Copyright 2021 FUJITSU LIMITED
CP
Line 1
28
P3AG-1812-06ENZ0