AB Quality 1794-IB16 Instrukcja instalacji

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Systemy wejścia/wyjścia AB Quality 1794-IB16. AB Quality 1794-IB16 17 stron. 24v dc flex i/o digital input modules

AB Quality 1794-IB16 Instrukcja instalacji
Installation Instructions
24V dc FLEX I/O
16 Sink Input Module
(Cat. No. 1794-IB16)
3
4

Module Installation

This module mounts on a 1794 terminal base unit.
1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 2
as required for this type of module.
2. Make certain the flexbus connector (3) is pushed all the way to the left
to connect with the neighboring terminal base/adapter. You cannot
install the module unless the connector is fully extended.
3. Make sure that the pins on the bottom of the module are straight so
they will align properly with the connector in the terminal base unit.
If you remove or insert the module while the
WARNING
backplane power is on, an electrical arc can occur.
This could cause an explosion in hazardous location
!
installations. Be sure that power is removed or the
area is nonhazardous before proceeding.
4. Position the module (4) with its alignment bar (5) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism (7) is locked into
the module.
FLEX I/O is a trademark of
Publication 1794 IN072C-EN-P - October 2001
Rockwell Automation
7
1
2
6
5