5.2 The indicator light is red
Potential errors and corrective actions:
•
Unsupported configuration on the eFiller charging current limitation. Check the position
on the DIP switches inside the charging point according to the table on page 7.
Notice that opening the cover can only be done by electrically skilled person.
•
Missing protective earth (PE). Check the PE availability from the supply line and condition
of the charging cable.
•
Error in the vehicle communication. Disconnect the vehicle, reset the charging point by
turning supply voltage off and on. Retry charging.
•
Software error. Disconnect the vehicle, reset the charging point by turning supply voltage
off and on. Retry charging.
•
The vehicle requires ventilation. In case the vehicle requires ventilation during charging,
eFiller does not allow charging.
5.3 The vehicle is charging slower than expected
•
Ensure from the vehicle that the vehicle has no timer charging activated. If the timer
charging is activated, the charging time may be different than expected.
•
Ensure from inside of the charging point the configuration of the current limitation DIP
switches. If the charging current limitation is set to a lower charging current than as-
sumed, the charging time is longer.
Notice that opening the cover can only be done by electrically skilled person.
•
Ensure that there is no charging current limitation features in use at the vehicle.
If you need to contact Ensto related to faulty operation of eFiller, please prepare to tell the
order number (V.......). You will find the order number on the nameplate on the enclosure bot-
tom.
6. Maintenance Instructions
With well-done maintenance you can ensure a long lifetime of the charging point and keep the
warranty valid.
Please proceed the following maintenance once in a month:
•
Test the residual current device (RCD-B) at the supply line. Usually RCD's have a test but-
ton for this purpose. There might be local requirements on the RCD manual test interval,
but Ensto recommends testing once a month. In case of failed test the RCD must be
changed.
•
Check the plug holder and the charging plug from possible dirt. Remove possible dirt.
•
Check the condition of the charging plug and the charging cable for wear out or mechani-
cal damage. If damaged, please replace necessary parts with new ones.
10