Brief operating instructions
Read and observe the safety instructions in chapter 1 of these operating
instructions.
Caution
Mechanical mounting
see fold-out drawing
Pneumatic connection
•
Connect the air supply to the in port. Air supply range must be between 1.4 and 6 bar
(20 to 90 psi).
Caution: Do not exceed the max. pressure of the actuator!
•
Connect the actuator supply to the OUT1 port (and OUT2 port for double acting actuators).
Electrical connection
•
Make the electrical connections according to the following terminal designation:
+11/-12
Analog input, 4...20 mA signal
+31/-32
Analog output, position feedback, 4...20 mA signal*
+41/-42
Digital position feedback, SW1 *
+51/-52
Digital position feedback, SW2 *
+81/-82
Digital input
+83/-84
Digital output, alarm contact
+41/-42
Kit for digital position feedback, Limit 2*
+51/-52
Kit for digital position feedback, Limit 1*
+41/-42
Shutdown module*
41
Kit for digital position feedback, 24 V microswitch, Limit 1, NC contact *
42
Kit for digital position feedback, 24 V microswitch, Limit 1, NO contact*
43
Kit for digital position feedback, 24 V microswitch, Limit 1, input*
51
Kit for digital position feedback, 24 V microswitch, Limit 2, NC contact*
52
Kit for digital position feedback, 24 V microswitch, Limit 2, NO contact*
53
Kit for digital position feedback, 24 V microswitch, Limit 2, input*
* Option
a
Brief operating instructions
Brief operating instructions
42/18-64-4 EN