19 - REMOTE CONTROLLER: HOW TO CHANGE FROM INFRARED TO WIRED
PREPARE THE REMOTE CONTROLLER
Detach the plastic cover of the remote controller terminal block.
Open the batteries compartment, remove the batteries and set microswitches 5 and 6 in OFF position.
Close the compartment without replacing the batteries (remote controller will be powered by wire).
CONNECTION
Use a tripolar electric shielded wire 0,5mm2, max. length 15m. The wires have not to be lighter than Mod. H05VVC4V5-
K (according to CEI 20-20 CENELEC HD21).
CONNECTING THE REMOTE CONTROLLER TO THE 5 POLES TERMINAL BLOCK INSIDE THE ELECTRICAL
PANEL, AS FOLLOWS:
Remove the "bridge" wire between the terminals 2 and 4.
Connect the terminal 1 to the bottom terminal of remote control terminal block (+ pole).
Connect the terminal 2 to the medium terminal of remote control terminal block (IR).
Connect the terminal 3 to the upper terminal of remote control terminal block (- pole).