19 - REMOTE CONTROLLER: HOW TO CHANGE FROM INFRARED TO WIRED
PREPARE THE REMOTE CONTROLLER
•
Detach the plastic cover of the remote controller terminal block.
•
Open the batteries compartment, remove the batteries and set microswitches 5 and 6 in OFF position.
•
Close the compartment without replacing the batteries (remote controller will be powered by wire).
CONNECTION
Use a tripolar electric shielded wire 0,5mm2, max. length 15m. The wires have not to be lighter than Mod. H05VVC4V5-
K (according to CEI 20-20 CENELEC HD21).
CONNECTING THE REMOTE CONTROLLER TO THE 5 POLES TERMINAL BLOCK INSIDE THE ELECTRICAL
PANEL, AS FOLLOWS:
•
Remove the "bridge" wire between the terminals 2 and 4.
•
Connect the terminal 1 to the bottom terminal of remote control terminal block (+ pole).
•
Connect the terminal 2 to the medium terminal of remote control terminal block (IR).
•
Connect the terminal 3 to the upper terminal of remote control terminal block (- pole).