Installation Procedures
4.2.5 Attach the Cisco 6160 Power Connections
Caution
To prevent the system from powering up, do not install the fuses at this time. If the fuses are already
installed in the fuse and alarm panel, remove them. You can replace the fuses after the system is installed
and connected.
For full power redundancy, each terminal block must be connected to a separate power source. If you do
Note
not require power redundancy, you can wire a single terminal block, or connect both terminal blocks to
a single power source.
Do not power the components in the rack by chaining them together.
Warning
The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated.
The proper wiring sequence is ground to ground, positive to positive, and negative to negative. The
ground wire must always be connected first and disconnected last. The fuse and alarm panel and
wires are not provided by Cisco.
Complete the following steps to connect power to the system:
Verify that power in the DC circuit is off.
Step 1
Identify the correct power terminal block on the backplane of the Cisco 6160. The PWR 1 connector is
Step 2
used if you have a primary PEM installed in the chassis. The PWR 2 connector is used if you have a
secondary (redundant) PEM installed in the chassis.
PWR 2 power terminal block connectors.
Step 3
Use a flat-head screwdriver and a counterclockwise motion to open the positive and negative terminal
connectors on the power terminal block.This step ensures that the correct opening is presented for the
wires. (See
Figure 4-8
Correct terminal
position (open)
Cisco 6160 Hardware Installation Guide
4-12
Figure
4-8.)
Positioning the Power and Ground Terminals to Accept Wires
Incorrect terminal
position (closed)
Chapter 4
Installing a Cisco 6160 Without a POTS Splitter Configuration
Figure 4-4
shows the location of the PWR 1 and
OL-2190-02 B0