Acuity Brands Lithonia Lighting D-Series Wall Instrukcje instalacji - Strona 4

Przeglądaj online lub pobierz pdf Instrukcje instalacji dla Oprawa oświetleniowa Acuity Brands Lithonia Lighting D-Series Wall. Acuity Brands Lithonia Lighting D-Series Wall 4 stron. Size 1 led light fixture

Installation Instructions
D-Series Size 1 LED Wall
Mounting the
D-Series Size 1 LED Wall
fixture to a back box (BBW):
Back box will be provided with (3) 3/4" NPT hole plugs, one on top and
on each side. (See Figure A).
See the back box in Figure B for the location of the cast-in drill point
indentations provided for Step 1 below.
Step 1: Drill the back box as shown in Figure B to prepare it for
1/4"anchor bolts (not provided) in 2 places with 9/32" drill.
Step 2: Place drilled back box against the wall, mark wall and drill for
the anchors (not provided).
Step 3: Install (2) anchors (not provided) securely into wall and attach
the back box. Install surface-mount conduit and secure with 3/4" NPT
locking nut (not provided). Do not over tighten.
Step 4: Secure green grounding wire from supply conductors to
grounding lug in back box.
Step 5: Apply bead of silicone sealant (not provided) around perimeter
of back box.
Step 6: Consult fixture installation instruction to complete installation.
Installing the
D-Series Size 1 LED Wall
Step 1: Take one of the wire guard brackets and place it against the edge of the cast housing. Locate the bracket hole 2-11/16" away from
the front of the housing as shown in Figure A. Use bracket as a drill guide. Use a #26 drill bit (.146 to .150 dia) and drill through in 2 places
taking care not to drill into the LED lights. Repeat these steps on the other side.
Step 2: Using a 1/4" hex drive, attach the wire guard brackets to the cast housing as shown in Figure B. The screws will create their own
threads in the holes you drilled in Step 1. Now take the remaining screws and attach the shield to the wire guard brackets.
2-11/16"
Edge of
casting
Installing the
D-Series Size 1 LED Wall
Step 1: Take one of the vandal guard brackets and place it against the edge of the cast housing. Locate the bracket hole 1-3/4" away from
the front of the housing as shown in Figure A. Use bracket as a drill guide. Use a #26 drill bit (.146 to .150 dia) and drill through in 2 places
taking care not to drill into the LED lights. Repeat these steps on the other side.
Step 2: Using a 1/4" hex drive, attach the vandal guard brackets to the cast housing as shown in Figure B. The screws will create their own
threads in the holes you drilled in Step 1.
Step 3: Take the vandal guard plastic shield and remove any protective film that it may have been shipped with. Now take the remaining
screws and attach the shield to the vandal guard brackets.
1-3/4"
Edge of
casting
Troubleshooting: If this fixture fails to operate properly, check to make sure: • The fixture is wired correctly.
correctly.
• The line voltage at the fixture is correct. If all these variables have been checked and the fixture still does not operate as
specified, contact your local Lithonia Lighting distributor.
©2010 Acuity Brands Lighting, Inc.
All Rights Reserved. 8/12
standard
Wire Guard
Wire guard
bracket
Figure A
Vandal Guard
Vandal guard
bracket
Figure A
Lithonia Lighting Outdoor • One Lithonia Way • Conyers, Georgia 30012
Phone: 800-279-8041 • Fax: 770.918.1209 •
© 2011 Acuity Brands Lighting, Inc. All rights reserved.
Figure A
Top view
Figure B
drill point
5-1/2"
indentation
2-5/8"
4-3/8"
Figure B
www.lithonia.com
Side view
13/16"
13/16"
11"
Figure B
• The fixture is grounded
Part Number:
RJ521349 Rev B
Revision Date: 6/3/14
1-3/4"
drill point
indentation