Function description

4
Function description
The two-channel evaluation unit of the safety switchgear module measures the frequency of the effective rotat-
ing field of the motor at the measuring terminals L1, L2, L3.
If the parameterized switching threshold frequencies are exceeded or undershot (V-LIMIT 1 and V-LIMIT 2), or an
internal or external fault exists, the enabling current paths 13/14, 23/24 open immediately. The device is in safe
switching state.
The monitoring of V-LIMIT 1 can be deselected. Then the output contacts remain closed at standstill.
Asynchronous motors have a load-dependent slip between the motor speed and the rotating field frequency. This
must be observed by the configuration of the switching threshold (V-LIMIT 1 and V-LIMIT 2).

Switching threshold

Two switching thresholds are configurable.
V-LIMIT 1: minimum speed
If V-LIMIT 1 is undershot, the output contacts (13-14 / 23-24) switch off.
They switch on again after the acknowledgment via the acknowledgment input Q.
Depending on the acknowledgment mode, the switch-on-conditions differ. Please note the chapter
"Function diagram".
V-LIMIT 2: Maximum speed
If V-LIMIT 2 is exceeded, the output contacts (13-14 / 23-24) switch off.
They switch on again after the acknowledgment via the acknowledgment input Q, if V-LIMIT 2 (minus hysteresis)
is undershot.
Switching on takes place at the earliest after 0.5 seconds. (see chapter minimum switch-off time)

Start-up monitoring

The startup monitoring t
mum speed is not reached during this time, the enable current path opens again.
The start-up monitoring time is fixed and is 60s. It is not retriggerable, it cannot be restarted while it is running.
The start-up monitoring time starts
In case of manual acknowledgment: with the falling edge of the acknowledge signal
In case of automatic acknowledgment: if the actual speed is> 1Hz
The startup monitoring is omitted if V-LIMIT 1 has been deselected.

Minimum switch-off time

The minimum switch-off time t
switches on again. It is 0.5s.

Acknowledge function

With the acknowledgment function, the enable current path is switched on again after a shutdown due to
underspeed or overspeed.
The acknowledgment takes place via the input Q.
Automatic or manual acknowledgment is possible.
With automatic acknowledgment, the Q input must always be connected to 24V DC.
A manual acknowledgment takes place after a falling signal edge at the input Q (t
8
is a time limit within which the actual speed must be greater than V-LIMIT 1. If the mini-
A
is the time that the enable current path is at least open after triggering before it
min
≥ 200ms and ≤ 10s).