DINA DN3PD1 Oryginalna instrukcja obsługi - Strona 9

Przeglądaj online lub pobierz pdf Oryginalna instrukcja obsługi dla Przyrządy pomiarowe DINA DN3PD1. DINA DN3PD1 20 stron. Speed monitoring for one and three phases motors without sensor system
Również dla DINA DN3PD1: Tymczasowa instrukcja obsługi (8 strony)

DINA DN3PD1 Oryginalna instrukcja obsługi
DN3PD1
Function description
Signal that is longer than10s does not cause a reset.
For parameterization of the acknowledgment function see chapter " Configuration of the switching
threshold and acknowledgement".

Functional diagram

Automatic acknowledgement V-LIMIT 1 and V-LIMIT 2
(V-LIMIT 1 must be at least 1.1Hz!)
f
V-LIMIT2
Hysteresis
Hysteresis
V-LIMIT1
1 Hz
0,5 Hz
t
A
13/14, 23/24
Q-autom.
1
2
3
1
Start-up monitoring time starts if f>1Hz
2
Start-up monitoring time is expired. Enabling
current path remains closed because f>V-LIMIT
1.
3
Enabling current path opens because f<V-LIMIT
1.
4
Enabling current path closes, if f<0,5Hz.
5
Start-up monitoring time starts if f>1Hz.
6
Start-up monitoring time is expired. Enabling
current path opens because f < V-LIMIT 1.
7
The setpoint speed was reached outside of the
minimum switch-off time. Enabling current path
closes.
8
The setpoint speed was reached within the min-
imum switch-off time. Enabling current path
closes after 0.5s.
18-09-27 / 33pd02-V0743
>t
t
min
A
4
5
6
7
Manual acknowledgment V-LIMIT 1 and V-LIMIT 2
f
V-LIMIT2
Hysteresis
Hysteresis
V-LIMIT1
<t
t
min
A
13/14, 23/24
Q-manuell
1
2
8
1
Start-up monitoring time starts with the falling
edge of the acknowledgement signal.
2
Start-up monitoring time is expired. Enabling
current path remains closed because f>V-LIMIT
1.
3
Enabling current path opens because f<V-LIMIT
1.
4
Start-up monitoring time starts with the falling
edge of the acknowledgement signal.
5
Start-up monitoring time is expired. Enabling
current path opens because f < V-LIMIT 1.
6
Start-up monitoring time starts again.
7
Start-up monitoring time is expired. Enabling
current path remains closed.
8
Enabling current path closes because
V-LIMIT 1<f<V-LIMIT 2.
t
t
A
A
3
4
5
6
7
8
9