Used in distance control RS485
F36
CALIBRATING IN PROGRESS
Used in distance control RS485 to know when calibrating end.
F38
THE MACHINE IS WAITING A COOLING DOWN DURING A CALIBRATION PROCEDURE
Wait please
F46
NO CURRENT SIGNAL
Verify sealing band connection,TA connection
F47
TA SIGNAL WRONG TURNED
TurnTA connection
F48
PRE-HEATING POTENZIOMETER NO CONNECTED OR CABLES BROKEN
Verify pre-heating potenziometer connections and cables
F49
SEALING POTENZIOMETER NO CONNECTED OR CABLES BROKEN
Verify sealing potenziometer connections and cables
F51
WIPER-I
Switch off and switch on the thermoregulator; if problem persist call the supplying
F52
WIPER-V
Switch off and switch on the thermoregulator; if problem persist call the supplying
F53
WIPER-VGROSS
Switch off and switch on the thermoregulator; if problem persist call the supplying
F54
WIPER-VFINE
Switch off and switch on the thermoregulator; if problem persist call the supplying
F60
RESET WITH CALIBRATING IN PROCESS
Repeat the calibrating
F61
BALANCE UNSUCCESSFULL
Repeat the calibrating
F62
BALANCE V UNSUCCESSFULL
Repeat the calibrating
F63
BALANCE VGROSS UNSUCCESSFULL
Repeat the calibrating
F64
BALANCE VFINE UNSUCCESSFULL
Repeat the calibrating
F65
BALANCE UNSUCCESSFULL
Repeat the calibrating
F66
MAIN PHASE SYNCHRONISM
Reset the thermoregulator if problem persist call the supplying
F69
CURRENT TO GROUND
Verify sealing bands in the machine touch ground.
F71
FAULT HARDWARE –15V INTERNAL
Reset the thermoregulator; if problem persist call the supplying
F72
FAULT HARDWARE +15V INTERNAL
Reset the thermoregulator; if problem persist call the supplying
F73
FAULT HARDWARE +5V INTERNAL REFERENCE
Reset the thermoregulator; if problem persist call the supplying
F76
IREAD TOO HIGH
Verify if short circuit on the seals
F78
THERMOREGULATOR NOT CALIBRATED
Do a calibrating
F79
FAULT OF EMERGENCY CIRCUIT
Verify contactor power, verify emergency chain
THERMOSALD ISC – MANUAL QUICK START
Manual cod.: 3ES080x_V5.1_QS_EN
Includes all previous models
Page Nr.