7 SILO FILLING INSTRUCTIONS

The DOMUSA TEKNIK Silo is designed to be filled by a tank truck, through a flexible hose that pumps
the pellets into the Silo. Tank trucks for pellet supply usually have a flexible hose of up to 30 metres,
and the Silo should therefore be installed at a maximum distance of 30 metres from the nearest truck
access point (if a longer distance is required, check with the pellet supplier whether longer hoses are
available). The truck access area must also have a minimum width of B = 3 m and a minimum
clearance of H = 4 m.
The filling nozzle must be accessible from outside the building, and so the premises in which the Silo is
installed must have at least one exterior wall. If this is not possible, the filling hose must be run to the
outside.
Ventilation duct
Ventilation duct
Boiler room
Filling nozzle
Silo
B=3 m
máx. 30 m
IMPORTANT: For safe Silo filling it is essential for the filling nozzle and supply hose to be earthed
during the filling process.
12