5.2.8 Switch on the battery backed power supplies connected to the module or connect the power
circuits to the terminals "+Umain" and "+Uback".
5.2.9 Put the module's cover on the place, close it and seal if necessary.
5.3 Maintenance Procedure 2
5.3.1 In accordance with the engineering documentation, decide upon:
The type of the system where the module is used,
Designation of the module,
Which network address is assigned to the module in the system,
Which power supply is connected to the module,
Which circuits and which devices the module monitors via "loop1" and "loop2" inputs,
Which devices are connected to the outputs "1", "2", "3", "4", "5", and "6' of the module,
Which network controller or device controls the module over the RS-485 interface,
Which control programs are assigned to each output in the configuration chart of the module,
Which events (or commands of the network controller) correspond to activation of the control
program at each used module's output,
How to generate the command or call the event to activate the control command for each used
output.
5.3.2 Open the cover of the S2000-KPB module removing the tamper label if necessary.
5.3.3 WARNING: If the module is connected to clean agent suppression modules or other
executive devices which must not be activated during the inspection, carry out the steps 5.3.4 – 5.3.7.
5.3.4 Switch off the battery backed power supplies connected to the module or disconnect the
power circuits from the "+Umain" and "+Uback" contacts.
5.3.5 Disconnect discharge circuits from the "+" and "−" contacts of used outputs of the module.
5.3.6 Connect discharge circuit simulators to the outputs as shown in Figure 5.
12
Figure 5. The schematic of a Discharge Circuit Simulator