7. Electrical connections
7.1 Basic information
Placement of installation and cabling have decisive influence on
the sensor's electromagnetic compatibility (EMC). Hence correct
installation of this active electronic system and the EMC of the entire
system must be ensured by using suitable metal connectors, shielded
cables and grounding. Overvoltages or faulty connections can damage
its electronics despite protection against wrong polarity.
NOTICE
1. Do not mount the sensors in the area of strong magnetic or
electric noise fields.
2.Never connect / disconnect the sensor when voltage is applied.
7.2 Safety recommendations
Be sure to:
1. Always follow applicable local and national electrical codes and
observe polarity when making electrical connections.
2. Never make electrical connections to the level transmitter with
power turned on.
3. Use low-resistant twisted pair and shielded cables. Connect the
shield to ground externally via the controller equipment.
4. Keep control and sign leads separate from power cables and
sufficiently far away from motor cables, frequency inverters, valve
lines, relays, etc.
5. Use only connectors with metal housing and connect the
shielding to the connector housing.
6. Keep the connection surface at both shielding ends as large as
possible. Connect the cable clamps to function as a ground.
7. Keep all non-shielded leads as short as possible.
8. Keep the earth connection as short as possible with a large cross
section. Avoid ground loops.
9. With potential differences between machine and electronics
earth connections, no compensating currents are allowed to flow
across the cable shielding. Recommendation: Install potential
compensating leads with large cross section or use cables with
separate double shielding, and connect only one end of the shield.
10. Use only stabilized power supplies in compliance with the
specified connecting values