TROUBLE SHOOTING
PROBLEM : The unit will not start
1 - Check the circuit breaker on your electrical panel.
2 - Check the circuit breaker of the unit. ( Image C1 )
3 - Check the 24 volt circuit:
To check the 24 volt circuit, proceed as follow ;
- Establish the contact between the two ports of a wall mounted air inlet
valve with a piece of metal (ex. coin ( Image D )). If the system starts, the
suction hose is defective. See your dealer.
- If the system does not start check the 24 volt wires on the unit ( Image C2 );
Establish the contact between the two screws of the 24 volts circuit plate
using a piece of metal (ex. Screw driver ( Image E )). If the unit starts,
the 24 volt wire is either cut OR unplugged from one of the wall mounted
air inlet valves.
- If the system still do not start after steps 1, 2 and 3, the printed circuit is
defective. Call your dealer.
PROBLEM : The unit will not stop
Check the 24 volt circuit as follows ;
- Disconnect one of the two 24 volt wires on the unit ( Image C2 ). If the
unit stops, the two wires are in contact somewhere in the circuit OR
a wall mounted air inlet valve is defective.
If the unit does not stop, the printed circuit is defective. Call your dealer.
NOTE : If you notice a vibration coming from the motor, call your dealer.