AirStage UTY-VSGXZ1 Manual de instalação - Página 3
Procurar online ou descarregar pdf Manual de instalação para Extensor AirStage UTY-VSGXZ1. AirStage UTY-VSGXZ1 6 páginas.
41
SELECTING AN INSTALLATION LOCATION
Dimensions
41 11
The signal amplifier is comprised of a body and cover.
Ø28 (1-3/32)
89.5
For dust proof
(3-17/32)
(3-17/32)
bushing
Ø22.2 (7/8) For conduit
241.6 (9-1/2)
272 (10-23/32) Hole pitch
288 (11-11/32)
4 - Ø5 (3/16) For M4x20mm screws
Power supply
Power consumption (W)
Operating
Temperature
Packaged
°C(°F)
Packaged
Humidity (%)
Dimensions
H x W x D mm(in1)
Weight g (oz1)
51
WIRING
WARNING
Before starting installation work, turn off the power of this unit and the
connection destination. Do not turn on the power again until installation
is completed. Otherwise, it will cause electric shock or fire.
Use the accessories or specified power supply cable and transmission
cables. Do not modify power supply cable and transmission cables
other than those specified, do not use extension cables, and do not use
independent branch wiring. Overcurrent may cause electric shock or fire.
Install the transmission cables securely to the terminal block. Confirm
that external force is not applied to the cable. Use transmission cables
made of the specified cable. If intermediate connection or insertion
fixing are imperfect, it will cause electric shock, fire, etc.
When connecting the power supply cable and transmission cable, route
the cables so that the cover of this unit is securely fixed. If the cover is
imperfectly fixed, it may cause fire or overheating of the terminals.
Perform earth (ground) work positively. Do not connect the earth
(ground) cable to a telephone cable, water pipe, or conductor rod.
Always fasten the outside covering of the transmission cables with the
cable clamp. (If the insulator is chafed, electric leakage may occur.)
Perform all wiring works so that the user does not touch the wiring.
Otherwise, injury or electric shock could result.
If any cable is damaged, do not repair or modify it yourself. Improper
work will cause electric shock or fire.
CAUTION
Do not bind the remote controller cable and the transmission cable
together with or parallel to the power supply cable of the indoor and
outdoor units. It may cause erroneous operation.
AMP Air Conditioning
Unit : mm (in.)
Ø28 (1-3/32)
89.5
For dust proof bushing
2-Ø5 (3/16)
For M4x20mm
screws
67
(2-5/8)
1Ø AC208–240V
50/60 Hz
4.5
0–46 (32–114)
-10–60 (14–140)
0–95 (RH); No condensation
67 x 288 x 211 (2-5/8 x 11-11/32 x
8-5/16)
1500 (53)
When performing wiring work, be careful not to damage the cable or
injure yourself. Also, connect the connectors securely. Loose connec-
tors will cause trouble, heating, fire, or electric shock.
Install the indoor and outdoor units, power supply cable, transmission
cable and remote controller cable 1 m (40 in.) away from television and
radio to avoid distorted images and noise. Otherwise, a malfunction
could result.
Perform wiring so that water does not enter this unit along the external
wiring. Always install a trap to the wiring or take other countermea-
sures. Otherwise it will cause trouble or electric shock or fire.
Confirm the name of each unit and name of each terminal block of the
unit and connect the wiring in accordance with the directions given
in the manual so that there is no incorrect wiring. Incorrect wiring will
damage the electric parts and cause smoke and fire.
When installing the transmission cables near a source of electromag-
netic waves, use shielded cable.
Otherwise, a breakdown or malfunction could result.
The terminal screws and earth (ground) screws have different shapes.
Be sure to install the screws in the correct locations. If the screws are
installed in the wrong locations, the PC board could be damaged.
There are some restrictions on the wiring condition.
For details, refer to the Design & Technical Manual.
Check point
51 11
▪
Arrange so that there is no transmission cable between each network
segment except the transmission cable which passed through the
signal amplifier.
▪
Arrange so that there is only 1 terminal resistor for each network seg-
ment.
Check the number of terminal resistors in each segment. If there
are more than 1 terminal resistor connected to the outdoor units and
signal amplifiers in a network segment, remove the additional terminal
resistors.
▪
Do not install a signal amplifier between 2 outdoor units in the same
refrigerant system.
▪
Install the disconnect switch to the easily accessible location.
▪
Install the fuse (3A) to the L line of power supply cable.
V Series
Signal amplifier (Filter mode : OFF)
1Ø 50/60Hz
FUSE
208-240V
(3A)
Switch
(Disconnect switch)
Indoor unit
Outdoor unit
Transmission cable
Terminal resistor
Indoor unit
V-II Series
Signal amplifier (Filter mode : OFF)
1Ø 50/60Hz
FUSE
208-240V
(3A)
Switch
(Disconnect switch)
Indoor unit
Outdoor unit
Transmission cable
Terminal
Indoor unit
resistor
www.ampair.co.uk | [email protected]
Terminal
resistor
Indoor unit
Refrigerant system
NS 2
NS 1
Terminal resistor
Terminal
resistor
Indoor unit
Refrigerant system
NS 2
NS 1
Terminal
resistor