Transmission cable
Cable
Cable tie holder
61 31
Installing the terminal resistor
CAUTION
Be sure to install the terminal resistors as specified. Install a terminal
resistor for each network segment.
If a terminal resistor is installed to more than 1 device in a single net-
work segment, the entire communication system may be damaged.
If a terminal resistor is not installed to any device in a single network
segment, communication errors may occur.
▪
Be sure to install 1 terminal resistor in a network segment. The termi-
nal resistor can be installed to an outdoor unit or to a signal amplifier.
▪
When a terminal resistor is installed to an outdoor unit, refer to the
installation manual supplied with the outdoor unit.
▪
When installing multiple terminal resistors, observe the following
conditions:
Divide the VRF system into multiple network segments.
(1)
Install a terminal resistor in each network segment. (Conditions
(2)
for 1 segment: total number of outdoor units, indoor units, signal
amplifier, touch panel controller and network convertor, etc.
must be 64 units or less, and the total length of the transmission
cables must be 500 m (1640 ft.) or less.)
▪
One terminal resistor is required for each network segment.
▪
When installing a terminal resistor, connect it between X1 and X2 of
CHA or CHB on the transmission terminal block.
▪
The terminal resistors have no polarity.
61 41
Filter mode setting
▪
Set the Filter mode to suppress an increase of the amount of com-
munication information in the VR-II system.
Indoor unit
VRF Series
number
–
V Series
–
V-II Series
2 to 320 units
321 to 400
VR-II Series
units
For the "Necessary" or "Not Necessary" details of Filter mode set-
*1.
ting, refer to the Design & Technical Manual for the VR-II .
●
: Necessary
○
: Not necessary
▪
Filter mode is turned on by inserting the accessory connecting wire at
the CN4 connector on the PC board.
▪
When the Filter mode setting is changed, turn the power off once.
Otherwise, the setting will not be recognized.
Connecting wire (Accessory)
Body
CN4
AMP Air Conditioning
Dust proof bushing
Cable tie
Cable tie
Connecting
Filter mode
wire
*1
○
OFF
○
OFF
○
OFF
●
○
/
ON / OFF
PC board
71
TURNING ON POWER
Cut
Check that the power supply voltage is within the specified range. If
the power supply voltage outside the specification is input, it will cause
trouble.
Recheck the wiring. Incorrect wiring will cause trouble.
Check the signal amplifier wiring.
(1)
Check the wiring and switch settings for the VRF system and turn
(2)
on the power for the VRF system. For the wiring and switch setting
method, refer to the installation manual of each unit.
Turn on the power for the signal amplifier.
(3)
▪
The signal amplifier is initialized for a period of approxi
onds after the power is turned on.
during this period.
▪
After initial setting completely, the operation mode will be
is displayed on D19-indicator.
Signal amplifier does not operate during initialization.
*
If an error occurs, the D9 or D14 LED lights or flashes, or the error
*
code is displayed on the right digit of the D19-indicator.
81
ADDRESS SETTING
When connecting multiple signal amplifiers, perform the
following address setting.
PC BOARD LAYOUT
AUTOMATIC ADDRESS SETTING
Turn on the power for the signal amplifier.
1.
2.
Confirm that D19-indicator indicates ADDRESS A1
ting: A1)
After checking, press the RESET button.
3.
4.
The address is set from an outdoor unit by the automatic operation.
(Refer to outdoor unit installation manual.)
When the automatic address setting and manual address setting are
mixed, the unit set to A2-A8 or A25-A56 in the manual address setting
is not intended for the automatic address setting.
*1.
When the automatic address setting is selected, the indicators
change is A9-A16 or A57-A88.
MANUAL ADDRESS SETTING
1.
Turn on the power for the
signal amplifier.
2.
While holding down SW4 (the
set button), press and release
SW7 (the reset button) to
enter the address setting
mode. The address setting
mode is activated only if the
set button is held down when
SW7 released.