ANDELI AJR3-1015 Manual de instruções - Página 3

Procurar online ou descarregar pdf Manual de instruções para Controlador ANDELI AJR3-1015. ANDELI AJR3-1015 15 páginas.

1. Concernment before operating

1-1 Inspection of incoming goods
After receiving the goods, please open the box to check the following items
to see if there is any problem on the products, if there is, or it is not your ordered
specification, please contact with the agent or the ANDELI office nearby.
To check the specification that on the nameplate of soft starter.
Nameplate
NAME
SOFT STARTER
TYPE
AJR3-1017
POWEY
17
VOLTAQE
AC380V50HZ
RATED CURRENT
SER.NO
Model of soft
A
JR 3
017 - 3
starter
Check the appearance to see if there is any damage that caused by transportation,
such as the outside cover and machine case. Also inspect the parts to see if there is
any damage or loose phenomenon.
Besides the soft starter, there is a copy of operating manual.
When carry the soft starter, please carry the machine body but not control box of
circuit board,
1-2 Product appearance
Machine base
Control box of circuit board
Nameplate
Connect with the motor
(2 T1、4 T2、6 T3)
KW
35 A
380V
Rated voltage:
Standard motor capacity:
017
17KW
055
55KW
Serial No.
AC soft starter
Enterprise Code
Coil in terminal of power
supply
(1 L1、3 L2、5 L3)
Keyboard panel
Communication interface
Terminal of control circuit
Connect with bypass contactor
(A2、B2、C2)
-1-

2. Installation and wiring

2-1 Operating environment
Table 2-1-1 indicates the requirements for operating environment
Table 2-1-1
AJR3-1000 develops the electronic soft start-soft stop
Standard :
deviceand has passed the performance test, complies
with national standard: (GB14048.6-98)
Three-phase supply voltage (U)
V
380-15%
Frequency
50
Hz
Suitable motor
Squirrel cage type three-phase asynchronous motor
Starting frequency
Please do not exceed 20 times per hour.
Degree of protection
Ip40 (Negotiable)
Resistance to impact
15g 11ms
Shock resistant capability
Altitude below 3000m, the vibratory force device below 0.5G.
Working temperature
Ambient
0...+ 40 no capacity-fall(+40~60℃,rise every 1℃,the
temperature
current will step down 1.2% )25...+70
Storage temperature
Ambient humidity
95% no condensation or drip
No capacity-fall when lower than 1000m (when higher than
Max working height
M
1000m, add every 100m, the current will step down 0.5%)
Cooling system
Cooled by natural wind.
Max operating angle relative
No requirement.
to the vertical installing position
2-2 Installing method
The soft starter should be installed vertically, never install it in inversion, gradient or level.
Make use of screw to install it in a firm structure.
When the soft starter runs, it will produce heat, in order to get enough cooling air, please
remain a certain space according to the diagram 2-2-1 during design. The heat produced will
emanate upwards, so please do not install the soft starter under the equipments that are not
thermal-resistant.
100
1/L1
3/L2
5/L3
50
50
READY
PASS
PERROR
准备
运行
故障
A
%
S
起动
RUN
设置
确认
停止
SET
YES
STOP
2/T1
A2
4/T2
B2
6/T3
C2
100
415+10%
440-15%
500+10%
Exhaust port
50
Admitting
图2-2-1
port
-2-