ANDELI AJR3-1015 Manual de instruções - Página 5

Procurar online ou descarregar pdf Manual de instruções para Controlador ANDELI AJR3-1015. ANDELI AJR3-1015 15 páginas.

2. Installation and wiring
2-5 Wiring diagram of main circuit of the ANDELI AJR3-1000 soft starter
3-phase power supply
50/60HZ
380V
L1 L2 L3
ON
OFF
1 L1 3 L2 5 L3
Motor soft
starter
(AJR3-1000)
B2
A2
2 T1 4 T2 6 T3
M
Equipped with
circuit breaker
(MCCB)
Or
(ELCB)
Leakage
circuit breaker
1 3 5
Equipped with
bypass electr-
omagnetic co-
ntactor
(KM)
2 4 6
C2
3-phase asynchronous motor
-5-
2. Installation and wiring

2-6 Wiring of control terminals

Please refer to the table 2-6-1 for the function of control terminals. According to different
function setting, the function and connection of the control terminals will be different.
Table 2-6-1
Classi-
Terminal
Terminal
fication
mark
name
When the soft start is finished starting, 01 and 02 closed
and control the bypass electromagnetic contactor.
Bypass
01, 02
output
03 and 04 are programmable relay output, the delay

Operation

time is set by code P4. Output function time is set by
output
03, 04
code PJ, as NO, close when the output is effective.
(Time delay)
(Contact rating AC 250V/3A).
05 and 06 are programmable fault relay output, they
Fault
will close when there is fault or it is power cut, and
05, 06
output
they will open when it is power on.
(Contact rating AC 250V/3A).
Instantaneous
When 07 and 10 are open, the motor will stop working imm-
07
stop input
ediately (or joining up in series with NC of other protectors).
Soft
When 08 and 10 open, the motor will speed down and
08
stop input
soft stop. (Or free stop)
Starting
When 09 and 10 close, the motor will start to run.
09
input
Common
The common terminal for contact to input signal.
10
terminal
11 and 12 is analog output for DC 4~20mA, it is used
to monitor the running current of motor, when it is full
Analog
11, 12
range 20mA, it is 4 times of nominal rated current, it
output
can be connected with 4~20mA ammeter for monitoring
signal outside, its max resistance of output load is 300Ω.
Commu-
The input/output signal terminal of RS485 commu-
RS485 communication
DB
nication, can be used to connect several soft starters.
nication
Input/output
(1) Contact input terminal
When use external terminals to control soft starter to start or stop, please set the
rnal control is effective.
If need remote control, we suggest using (two wires) control mode, please refer to 2-8 in Page 8
(two wires control mode).
Usually, the contact signal input terminal and common terminal will do close/open (ON/OFF)
actions, the soft starter, motor and conductor arrangement will produce interference, therefore,
please use shorter wire (shorter than 20m), and use shielding conductor for cable.
The conductor arrangement of control terminal should be far away from the wiring of main
circuit. Otherwise, there may be error operation caused by interference.
Function description
01
FU
L1
02
A1 A2
N or L3
P
D into exte-