Integrated Access Controller – Installation manual
Relay Setting (Pulse mode, Toggle mode)
Pulse mode (Factory default)
Pulse mode ( Door relay time setting )
Toggle mode
Toggle mode
Door Detecting, Alarm, Sound and Light Settings
Door Open Detection
Door Open Too Long (DOTL) warning. When used with an optional magnetic contact or built-in magnetic con-
tact of the lock, if the door is opened normally, but not closed after 1 minute, the inside buzzer will beep auto-
matically to remind people to close the door and continue for 1 minute before switching off automatically.
Door Forced Open warning. When used with an optional magnetic contact or built-in magnetic contact of the
lock, if the door is opened by force, or if the door is opened after 20 seconds of the electro-mechanical lock
not closed properly, the inside buzzer and alarm output will both operate. The Alarm Output time is adjustable
between 0~3 minutes with the default being 1 minute.
Alarm output time
To set the alarm output time (0~3 minutes)
Door open detection setting
To disable door open detection
(Factory default)
To enable door open detection
Keypad Lockout & Alarm Output options. If there are 10 invalid cards or 10 incorrect PIN numbers in a 10
minute period either the keypad will lockout for 10 minutes or the alarm will operate for 0~3 minutes, depend-
ing on the option selected below.
Normal status: No keypad lockout or alarm
(factory default)
Keypad Lockout
Alarm Output
Light and Sound Setting
To set keypad backlight
To set LED
To set Acoustic Signal
The acoustic signal can be set on or off.
When on, the device will give the voice
when press the keys; when off, the device
will be in silent.
All rights reserved. © AAT HOLDING S.A.
4 1 1~99 # Zone 1
4 2 1~99 # Zone 2
The door relay time is between 1~99 seconds, the factory de-
4 1 0 # Zone 1
4 2 0 # Zone 2
5 0~3 # Factory default is 1 minute
6 0 #
6 1 #
7 0 # (Factory default)
7 1 #
7 2 #
81 0 # To disable keypad backlight
81 1 # To enable keypad backlight (Factory default)
82 0 # To disable the RED Led
82 1 # To enable the RED Led (Factory default)
83 0 # To disable the keypad tone
83 1 # To enable the keypad tone (Factory default)