Dukane iQ LS-E Nota de aplicação - Página 13

Procurar online ou descarregar pdf Nota de aplicação para Fonte de alimentação Dukane iQ LS-E. Dukane iQ LS-E 16 páginas. Ultrasonic probe system, automation interface guidelines

DUKANE
Intelligent Assembly Solutions
iQ LS / LS-E Automation Controlled Probe Generator Timing Diagrams
L
S
/
L
S
-
E
(
W
e
l
d
-
b
y
-
L
S
/
L
S
-
E
(
W
e
l
d
-
b
y
-
Normal Weld Cycle - A normal weld cycle lasts as long as the U/S Activate input is in a high state. This cycle shows the
timing between activation/deactivation of the U/S Activate input, U/S Status output and Ready Status output signals.
The Ready Status Output: The Ready Status output is used to determine if the generator is ready to start a new weld
cycle. As seen in Figure 1, the Ready Status output requires a minimum of 3ms to change to its deactivated state after the
U/S Activate input is activated. For correct operation, a PLC controlling an LS or LS-E Automation generator must delay at
least 3ms after activating the U/S Activate input before checking the Ready Status output. At the end of a normal cycle,
the Ready Status output requires a minimum of 19.5ms to change to its activated state after the U/S Activate input has
deactivated. For correct operation, a PLC controlling an LS or LS-E Automation generator must delay at least 19.5ms
after deactivating the U/S Activate input before checking the Ready Status output. It is possible that the stack ring down
time (stack stops vibrating), which is stack and application dependent, will make this time much longer.
The U/S Status Output: The U/S Status output is used to determine when the generator has activated its ultrasound
ouput to the ultrasonic stack. As seen in Figure 1, the U/S Status output requires a minimum of 5ms to change to its
activated state. For correct operation, a PLC controlling an LS or LS-E Automation generator must delay at least 5ms after
activating the U/S Activate input before checking the U/S Status output. At the end of a normal cycle, the U/S Status
output requires a minimum of 18.0ms to change to its deactivated state after the U/S Activate input has deactivated. For
correct operation, a PLC controlling a LS or LS-E Automation generator must delay at least 18.0ms after deactivating the
U/S Activate input before checking the U/S Status output.
Weld Cycle with an Overload - This weld cycle shows the same timing relationship as a normal weld cycle except the
ultrasound output, indicated by the U/S Status output, is terminated early due to an overload condition.
The Any Fault Status Output: The Any Fault Status output is used to determine when the generator has terminated the
weld cycle due to an overload. When an overload occurs, the Any Fault Status output activates at the same time the U/S
Status output deactivates. The Ready Status output doesn't activate until the U/S Activate output deactivates. The Ready
Status output requires a minimum of 20.0ms to change to its activated state after the U/S Activate input has deactivated.
For correct operation, a PLC controlling an LS or LS-E Automation generator must delay at least 20.0ms after deactivating
the U/S Activate input before checking the Ready Status output.The Any Fault Status output will deactivate the next time
the U/S Activate input is activated, but is delayed up to 3ms.
The Overload Status Output: The Overload Status output is also used to determine when the generator has terminated
the weld cycle due to an overload.The Overload Status output has the same timing as the Any Fault Status output and will
deactivate the next time the U/S Activate input is activated, but is delayed up to 3ms.
AN502 (REV 07)
Page 13 of 16
A
u
t
o
m
a
t
i
o
n
)
T
i
m
i
n
g
A
u
t
o
m
a
t
i
o
n
)
T
i
m
i
n
g
Figure 1: LS / LS-E Weld-by-Automation Cycle Timing Diagram
D
i
a
g
r
a
m
D
i
a
g
r
a
m
APPLICATION NOTE
AN502
© Dukane 2016. All Rights Reserved.