Cookson FCA Manual de instruções - Página 10
Procurar online ou descarregar pdf Manual de instruções para Abertura de portões Cookson FCA. Cookson FCA 17 páginas. M100 firegard chain; m100 firegard crank
TERMINAL CONNECTIONS
Disconnect power supply before servicing.
WARNING
TB1
L1
Input power 115VAC*, Not Supervised
TB2
+
-
1 (
)
2 (
)
Input 24VDC/VAC
Use Power Limited source
only
Not Supervised
*Note. 4
*Note:
1. Terminal 3&4
Building fire alarm panel (FACP) needs to provide dry contact (N/C) connection with minimum capacity of 24VDC and 0.5 amp.
Terminal 4
When connecting more than one wire/connector to the terminal, must use enclosed Part # CDA-FH600-WHF02. See page 13 for
illustration.
2. Terminal 6&7
This connection provides 24VDC, 1A power with 18AWG wire for maximum of 20 ft. Upon alarm signal, this connection can be
used to provide power for warning devices. The warning power is provided for less than a minute. The wiring connections are
enclosed within conduit or equivalently protected against mechanical injury.
3. Terminal 8&9
These terminal connections will provide the status of this release device. When release device is in the standby mode, connection is
open (N/O). When release device have been activated or released, connection would be in closed (N/C) state.
4. See connection chart for power inputs. A regulated, power limited UL1481 Power Supply must be used for this terminal.
L2
See Note. 4
3
4*
Alarm Dry Contact (N/C)
Not Supervised *Note 1
Close button
Dry contact (N/C)
5
6
Alarm door close warning
24VDC, total 1A
Common, Not Supervised
*Note 2
9
7
8
Brake release status
(Dry contact)
24VAC/VDC, 2A Max.
Resistive load, Common,
Not Supervised
*Note 3
TM
M100 FireGard
Chain & Crank
9
02/11