SYSTEM INSTALLATION AND WIRING
––––––––––––––––––––––––– INSTALLING THE SYSTEM –––––––––––––––––––––––
Refer to the Summary of Connections diagram on the inside back cover of this manual for terminal
connections when following these procedures.
1. Mount the Control Cabinet.
2. Mount the PC board.
WARNING
3. Install Remote Keypads.
4. Install Hardwired Zones.
5. Install Sounding Devices.
U L
6. Install the Remote Keyswitch.
7. Connect Telephone Line.
IMPORTANT
8. Connect the AC Transformer.
WARNING
9. Connect the Battery.
IMPORTANT
U L
11.
Connect Earth Ground.
Section 2.
BE SURE TO USE THE PLASTIC MOUNTING CLIPS (SUPPLIED) TO
ISOLATE THE CIRCUIT BOARDS FROM THE CABINET. FAILURE
TO DO SO MAY RESULT IN DAMAGE TO THE TRANSFORMER
AND/OR THE CIRCUIT BOARDS.
Use only UL Listed sounding devices for UL installations.
Make sure telephones on the premises are connected only through the
alarm control panel (disconnect from the incoming phone line at the
telephone jack). This is necessary to have true line seizure.
DO NOT PLUG THE TRANSFORMER INTO THE AC OUTLET UNTIL
ALL OTHER WIRING TO THE CONTROL IS COMPLETE.
Do not attach the connector cable to the battery's terminals until
after you have plugged the AC transformer into an uninterrupted
120VAC outlet.
1. In UL installations, maximum current draw from the Auxiliary
Output and the Alarm Output combined must not exceed 500mA.
2. Use a 3A battery or larger for UL installations.
-8-