FAN SWITCHES (FS 1 / 2 / 3)
These terminals can be connected to a fan switch (supplied separately) which provide power to fans
when the emergency shut-off button is pressed.
Example of an AGS FS1 given.
CO2 MONITOR & 12VDC
Primarily this is used to power the AGS CO2-X but can be used as a power output for external auxiliary
devices when there is power at the panel and can be used to create a relay switch with the BMS relay
output. Max output: 50mA. If no CO2 monitor or other device is connected, the panel will 'beep' upon
power up and the CO2 LED will flash 3 times to indicate that this terminal has been disabled.