Installation, Operation & Maintenance
Power and Modbus data are wired between detectors with the first connected to a ParkSafe controller
[Detector Chain] terminal. If using a shielded wire (recommended) then connect the shield to [Shield Wire]
dedicated terminals.
Up to sixteen (16) ParkSafe detectors can be connected, chained in a parallel 'daisy chain' method up to
approx. 545 yards from the controller depending on chain configuration, wire type and condition. Any other
way may cause issues or damage to the overall system.
It is recommended that the cable of same color should be used to connect all [D+] terminals together and
similarly cable of same color is used to connect all [D-] terminals together.
Single chain example.
Split chain example
Rev: 20
For Modbus communications, a shielded cable is used.
The shielding can be of 2 types: braided [mesh of thin conducting wires] or
foil (consisting of a thin sheet of metal covering the twisted wires).
One example of such cable is BELDEN 3082A.
ParkSafe Controller
8