Fujitsu 24LMAS1 Manual de instalação - Página 5

Procurar online ou descarregar pdf Manual de instalação para Ar condicionado Fujitsu 24LMAS1. Fujitsu 24LMAS1 17 páginas. Outdoor unit

Fujitsu 24LMAS1 Manual de instalação

3.1. Installation dimensions

Keep the space shown in the installation examples.
If the installation is not performed accordingly, it could cause a short circuit and result
in a lack of operating performance.
3.1.1. Single outdoor unit installation
When the upward area is open [Unit: in (mm)]
(1) Obstacles at rear only
4 (100)
or more
(3) Obstacles at front only
20 (500)
or more
When an obstruction is present also in the upward area [Unit: in (mm)]
(1) Obstacles at rear and above
Max.
19 (500)
40
(1,000)
or more
12 (300)
or more
3.1.2. Multiple outdoor unit installation
• Provide at least 10 in (250 mm) of space between the outdoor units if multiple units
are installed.
• When routing the piping from the side of an outdoor unit, provide space for the piping.
When the upward area is open [Unit: in (mm)]
(1) Obstacles at rear only
10 (250)
12 (300)
or more
or more
(3) Obstacles at front and rear
10 (250)
or more
CAUTION
(2) Obstacles at rear and sides
4 (100)
4 (100)
or more
or more
10 (250)
or more
(4) Obstacles at front and rear
4 (100)
or more
20 (500)
or more
(2) Obstacles at rear, sides, and above
Max.
19 (500)
20 (500)
8 (200)
or more
or more
10 (250)
or more
(2) Obstacles at front only
10 (250)
or more
60 (1,500)
or more
20 (500) or more
60 (1,500)
or more
When an obstruction is present also in the upward area [Unit: in (mm)]
(1) Obstacles at rear and above
• Up to 3 units can be installed side by side.
• When 4 units or more are arranged in a line, provide the space as shown below.
Max.
11 (300)
10 (250)
or more
3.1.3. Outdoor units installation in multi row
(1) Single parallel unit arrangement
(2) Multiple parallel unit arrangement
40
(1,000)
or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there
is no obstacle.
• When installing the outdoor unit, be sure to open the front and left side to obtain
better operation efficiency.

3.2. Transporting the unit

Do not touch the fins. Otherwise, personal injury could result.
When carrying the unit, hold the handles on the right and left sides and be careful.
If the outdoor unit is carried from the bottom, hands or fingers may be pinched.
• Be sure to hold the handles on the sides of the unit. Otherwise, the suction grilles on
the sides of the unit may be deformed.
Handle
60 (1,500)
or more
20 (500) or more
[Unit: in (mm)]
6 (150) or more
119 (3,000) or more
24 (600) or more
60 (1,500) or more
20 (500) or more
138 (3,500) or more
24 (600) or more
60 (1,500) or more
WARNING
CAUTION
Handle
60
(1,500)
or more
En-5