DFE TRUETENSION TA1 Manual de início rápido - Página 9

Procurar online ou descarregar pdf Manual de início rápido para Amplificador DFE TRUETENSION TA1. DFE TRUETENSION TA1 12 páginas. Tension amplifier
Também para DFE TRUETENSION TA1: Manual de instruções (16 páginas)

DFE TRUETENSION TA1 Manual de início rápido
Normal Operation = Solid Green
1 BLINK = No Calibration Performed
Action Required:
Perform Calibration. TA1 is not factory calibrated. A calibration
must be performed at the customers site. Each calibration is specific to the
installation configuration. If using CAL B – a separate calibration must be performed.
2 BLINKS = Outside Cal Range
Once calibrated the TA1 will indicate an over range or under range condition by
setting the error code to 'Outside Cal Range' . The error is active once -20% or 120%
tension is exceeded.
Action Required:
To clear this error the tension must be brought back into rang, or
a new calibration will need to be performed to do so.
3 BLINKS = Wiring Error
Will alert until the load cell are wired correctly.
Action Required:
Check wiring and retry. Refer to page 4. Check for loose wires at
the terminal blocks, check for shorts, and be sure the load cells are connected. If the
transducers need trouble shooting – contact tech support for assistance.
Overload Condition (LT Transducer):
Will intermittenly alert if overload is reached.
Action Required:
Check that the tension range does not exceed the transducer
load rating. Reduce wrap angle to reduce effective net force exerted on load cell.
TROUBLESHOOTING
7