Verify the Application
Ensure V1K is correct for the application. Current
rating of the V1K should be sized to handle the FLA
rating of the motor but not exceed 110% of the drive
output current rating. This V1K is best applied matched
closely to the load. The V1K is not selected by the drive
input current rating. Properly sized and applied, TCI
guarantees that the V1K will limit motor terminal peak
input votage to 150% of bus voltage with a wire lead
length of 1,000 feet and a carrier frequency of 4kHz. Max
lead length and carrier frequency can vary depending on
wire lead type. For best performance, the V1K should be
installed within 10 feet of the drive.
Power Wiring
The conduit and wiring from the output of the VFD to the
motor must be routed to the V1K and then to the motor.
TCI recommends a separate dedicated conduit run for
each drive/filter/motor run unless properly shielded and
segregated wiring procedures are practiced. Parasitic
and induced capacitance can greatly reduce the
effectiveness of the filter. Under no circumstances should
you wire both control and power wire in the same conduit
unless the wireway is specifically designed for this
practice. The line reactor temperature is sensitive to lead
wire oversizing. Avoid lead wires more than five times
oversized by copper cross sectional area regarldess of
the material used. Use 75°C copper conductors only or
the equivalent, unless the wire connector is marked for
AI/Cu, then the use of aluminum wire is permitted. Use
only copper conductor on units rated above 80 amps.
Grounding
The V1K filter must be connected to the ground of the
premises wiring system. Connect the filter to a known
ground nearby the filter or run a special ground wire
dedicated for the application. The ground connection
must be made using a wire conductor. Metallic conduit
is not a suitable grounding conductor. The integrity of all
ground connections should be periodically checked.
Variable Frequency Drive Settings
Make sure that the VFD will be set for operation modes
and ranges that are compatible with the V1K:
•
Maximum output frequency: 60 Hz
•
PWM switching frequency: 2 kHz and 4 kHz
•
Mode of operation: Do not use filter on 600 VAC
systems with Dynamic DC braking resistors or
Active Front End drives
•
Do not use on overhauling loads without bus
voltage control.
KDR Reactor Lug Kits
Follow NEC guidelines to determine acceptable wire ampacity requirements.
Fig.
Lug Kit
Lug Wire Range
Number
SLK10
1
2/0 - 14 AWG
SLK13
2
(2) 350 kcmil - 6 AWG
SLK14
2
(2) 600 kcmil - 4 AWG
SLK16
3
(3) 600 kcmil - 2 AWG
SLK21
1
250 kcmil - 6 AWG
SLK22
4
(2) 2/0 - 14 AWG
Lug Torque Tables
Table S2/0
Wire Size Copper (solid
Rating
to semi-rigid stranded
C
and metric mm, ##)
N/A
90
N/A
90
2/0 - 3 AWG
90
4 - 6 AWG
90
8 AWG
90
10 - 14 AWG
90
Table S250
250 kcmil-2 AWG
90
(1),(2) 25-16 mm
(1) 35
2
90
mm
2
Table 2S350
350 kcmil- 2 AWG
90
2 - 6 AWG
90
Table 2S600
BNVN
90
CSA, 200116
UL Listed 84JM ZMVV E129884
Table T3A2-600N
• T3A2-600N;
• CSA Certified
• UL 486A/B Listed, UL File E6207
• Must be mounted with a minimum of 2 bolts
Item ID
Conductor Range
T3A2-600N
600 kcmil-2AWG
For Lug Torque
See Table S2/0
66 lb-in (7.5 N-m)
See Table 2S350
450 lb-in (50.8 N-m)
See Table 2S600
450 lb-in (50.8 N-m)
See Table T3A2-600N
450 lb-in (50.8 N-m)
See Table S250
66 lb-in (7.5 N-m)
See Table S2/0
66 lb-in (7.5 N-m)
IHI Connectors
Wire Size FLEX
Wire Size
Copper (#)
Aluminum
1/0 - 1 AWG
N/A
1 - 4 AWG
N/A
4 - 8 AWG
2/0 - 3 AWG
8 - 10 AWG
4 - 6 AWG
10 - 14 AWG
8 AWG
N/A
10 - 12 AWG
IHI Connectors
3/0-2 AWG; 70-50 mm
250 kcmil - 2 AWG
2
2-6 AWG; 35-16 mm
2 - 6 AWG
2
IHI Connectors
262 kcmil - 2 AWG
350 kcmil - 2 AWG
2 AWG - 4 AWG
2 - 6 AWG
IHI Connectors
444 kcmil - 2 AWG
600 kcmil - 4 AWG
(#) FLEX-covers stranding classes within G, H, I/DLO, Metric
class 5 and K/MTW, (##) mm
sizes within AWG/kcmil ranges are
2
included
Ilsco
Bolt/Stud Size
1/2
Bolt Assembly
See Website For Lug On
Torque
Reactor Drawings
See Drawing (LK10-DWG)
See Drawing (LK13-DWG)
See Drawing (LK14-DWG)
See Drawing (LK16-DWG)
See Drawing (LK21-DWG)
See Drawing (LK22-DWG)
Torque
(all drive means)
75 lb-in (8.5 N-m)
55 lb-in (6.2 N-m)
50 lb-in (5.6 N-m)
45 lb-in (5.1 N-m)
40 lb-in (4.5 N-m)
35 lb-in (4.0 N-m)
375 lb-in (42.4 N-m)
275 lb-in (31.1 N-m)
375 lb-in (42.4 N-m)
275 lb-in (31.1 N-m)
500 lb-in (56.5 N-m)
Hex Size
Tightening Torque
1/2
500 lb-in (56.5 N-m)
Figure 1
Figure 2
Figure 3
Figure 4