CP Electronics ALC-PRM-VFC Manual do produto - Página 5
Procurar online ou descarregar pdf Manual do produto para Acessórios CP Electronics ALC-PRM-VFC. CP Electronics ALC-PRM-VFC 8 páginas. Ceiling mounted photocell
Parameter Name
Default Value
Detector Parameters
Lux time
0
Factory default
-
Switching functions
Lux on level
9
(Switch level on)
Lux off level
9
(Switch level off)
User Modes
-
Override On
Override Off
-
Cancel
-
Range / Options
Description
0 (disabled)
To prevent nuisance switching, an adjustable time delay can be set. This requires
the light level to be maintained for the set time before changing from on to off, or
1-99 minutes
off to on.
-
Restores factory default settings
1 to 9
Lux level setting to prevent the luminaires being switched on if the ambient light
level is sufficient.
For a higher
Note: the Lux Level Off value must always be greater than the Lux Level On value.
resolution a scale
of 101-199 is
available
1 to 9
Lux level setting to switch the luminaires off the ambient light level goes above the
setting.
For a higher
resolution a scale
of 101-199 is
available
-
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period .
-
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancels the on or off override, returning the unit to normal operation.
-
Advanced programming
UHS5 UNLCDHS
5