HP 1410-24G-R Manual de iniciação - Página 7

Procurar online ou descarregar pdf Manual de iniciação para Interruptor HP 1410-24G-R. HP 1410-24G-R 21 páginas. 1410 switch series
Também para HP 1410-24G-R: Especificação (33 páginas), Especificação (33 páginas), Manual de configuração rápida (2 páginas)

HP 1410-24G-R Manual de iniciação
Table 3 Dust concentration limit in the equipment room
Substance
Dust
NOTE:
Dust diameter ≥ 5 μm
The equipment room must also meet strict limits on salts, acids, and sulfides, as shown in
eliminate corrosion and premature aging of components.
Table 4 Harmful gas limits in the equipment room
Gas
SO
2
H
S
2
NH
3
Cl
2

ESD prevention

To prevent electrostatic discharge (ESD), follow these guidelines:
Ground the switch correctly.
Take dust-proof measures for the equipment room.
Maintain the humidity and temperature at a proper level.
Always wear an ESD-preventive wrist strap. Make sure the wrist strap makes skin contact and is well
grounded.
NOTE:
The ESD-preventive wrist strap is not provided with the switch. Order it yourself.

EMI

All electromagnetic interference (EMI) sources, from outside or inside of the switch and application
system, adversely affect the switch in the following conduction patterns:
Capacitance coupling
Inductance coupling
Electromagnetic wave radiation
Common impedance (including the grounding system) coupling
Cables (power cords, signal cables, and output cables)
To prevent EMI:
If the AC power supply system is a TN system, use a single-phase three-wire power receptacle with
protection earth (PE) to filter interference from the power grid.
Concentration limit (particles/m³)
≤ 3 × 10
(no visible dust on the tabletop over three days)
4
Maximum concentration (mg/m³)
0.2
0.006
0.05
0.01
4
Table
4, to