3. Output Voltage Reconfiguration Procedure
Some systems may require reconfiguring the output voltage setting. If necessary, follow the steps below to complete the
procedure. If the factory default satisfies your system requirements, proceed to Section 3.
NOTE:
The output voltage factory default is 63 Volts.
Tools Required:
Small flat-blade screwdriver.
1. To access output voltage terminal, remove the Inverter Module.
2. Loosen the terminal screw and move the output voltage wire (Fig. 1)
to the desired output voltage position on the terminal strip.
3. Torque the terminal block screw to 0.79N-m to secure the output
voltage wire.
4. Replace the Inverter Module.
4. Output Power Connection Plate (AlphaPOP)
Output Power Connection Plate: The XM3V-HP has three different AC output
connector options.
16
8-Position Output Terminal: Each Output can be isolated from other
Outputs.
2 x 2 Output Terminal: This connector option has two terminal block
17
connectors and two coaxial connectors. Each Output can be isolated
from other Outputs.
4-Position Coaxial Connection (White = Neutral, Black = Line): Each
18
Output can be isolated from other Outputs.
5. DOCSIS Communications Module
Front Panel Connections
1. Connect the Battery Sense Harness
(SAG) option, connect the Battery Harness to the SAG Connector
Supply.
2. Connect Tamper Switch Wire Harness to the TPR Connector
3. Connect the RF drop to the RF Connector
NOTE:
The DOCSIS specification for downstream power level is 0 dBmV, +/- 15 dBmV. The upstream power level should not
exceed +50 dBmV.
Ethernet Connector
Green/Blue/Red
LED Indicators
To Battery Sense Wire Harnesses
6
to the A/B or C/D Connector . For XM3V units with the Smart AlphaGuard
.
7
8
13
7
6
Fig. 1 - Output voltage wire and terminal bar.
16
OUTPUT 1
OUTPUT 1
17
OUTPUT 1
OUTPUT 1
18
OUTPUT 1
OUTPUT 1
located on the left side of the XM3V Power
11
8
.
Tamper Switch (TPR) Connector
RF Cable to Headend
Required
Grounded Surge Protector
(Alpha p/n 162-028-10 or equivalent)
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
~ N ~ N ~ N ~ N
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
~ N ~ N ~ N ~ N
OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4
~ N ~ N ~ N ~ N
AC OUTPUT
~
N
OUTPUT 4
AC OUTPUT
~
N
OUTPUT 4
AC OUTPUT
~
N
OUTPUT 4
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 2
OUTPUT 3
OUTPUT 4