Alpha Outback Energy CableUPS XM3V-HP Manual de início rápido - Página 5
Procurar online ou descarregar pdf Manual de início rápido para UPS Alpha Outback Energy CableUPS XM3V-HP. Alpha Outback Energy CableUPS XM3V-HP 7 páginas.
6. Power Module Con��ration
and Output Voltage/Current
Describes Power Supply
Mode of Operation
Describes Status of Functions
Functionality top level menu
PWR, BATT, COMM and APPS
Softkeys (Menu driven
system configuration)
Installation Procedure
CAUTION!
Before applying power, verify power supply rating is matched to AC input utility. Verify a low-resistance ground is
installed in accordance with the NEC (refer to CableUPS Power Supply technical manual for details).
1.
After wiring battery cable kit, battery sense cables and PTS, as shown in
Section 1, verify DC breaker is OFF.
2.
Connect the Smart AlphaGuard (SAG) wire harness to SAG port
SAG is installed, connect battery sense harness to the transponder
3.
Connect PTS to the PTS connector
4.
Connect the RF cable
5.
Connect the network load to the Output 1 connector.
6.
Connect the additional network isolated load / auxiliary load (i.e., fan) to the
Output 2-4 connectors.
4
7.
Connect the LRI
to the XM3V.
8.
Turn ON AC breaker and verify it is the correct utility voltage at the outlet (per
unit's nameplate voltage). If correct, plug in the line cord into the utility outlet.
9.
Verify correct battery voltage and polarity on battery cable connector with a
digital voltmeter, if correct plug into Inverter Module
10. Turn battery breaker ON
11. Verify no alarms are present after power up initialization. Wait for alarms to
clear (approximately 60 seconds).
12. If no alarms are present, proceed to Step 16.
13. If alarms are present and do not clear after 60 seconds, press the softkey with
ALM
C
to see the ACTIVE ALARM list for the menu item.
14. Press UP (↑) or DOWN (↓) to select the alarm of interest.
15. Press ENTR to select the alarm and display diagnostic information. Press
ESC to return to the alarm list.
16. On the SmartDisplay, press the BATT softkey, enter the BATT CONFIG
menu and select BATT MODEL and NUM BATT STRINGS (Fig. 2).
17. On the SmartDisplay, press BATT softkey, enter BATT CONFIG, enter BATT
MHOs* and DATE Code (Fig. 3).
*Note: Battery MHOs and Date code can only be set after DOCSIS
transponder has registered with CMTS. Please wait 3 minutes after
power up to enter Battery MHOs measurements.
18. Switch SPI / ALT Box Switch to ON, verifying the load on the XM3V.
19. Perform a self-test by pressing and holding the Test Button
seconds. Wait for self-test completion before proceeding.
20. Perform standby test by shutting OFF utility breaker and verifying it goes into
STANDY MODE and supports the load.
21. Reapply AC power and verify the unit transfers to LINE MODE.
Indicates Model
A
B
C
D
3
.
7
and the tamper switch
8
2
.
A
XM3V-618CE-HP
C
OK
D
PWR
E
11
. If no
6
.
to the transponder.
1
.
I
for 1-2
63V/0.4A
B
OPERATION NORMAL
ALM
OK
BATT
COMM
XM3V-618CE-HP
63V/0.4A
**ACTIVE ALARM**
OK
PM
ALM
PWR
BATT
COMM
OUTPUT LED (green)
G
H
SOLID = Operation Normal
FLASHING = Minor Alarm
OFF = Major Alarm
SELF TEST BUTTON
I
Press button to initiate self test.
hi 8
EDIT USING
BATT MODEL
ENTR
h
i
Fig. 2 - Battery Model input
BATT
A1
DATE
hi
ADJUST VALUE
���������
ENTR
h
i
BATT
A1
MHOs
hi
ADJUST VALUE
ENTR to save
ENTR
h
Fig. 3 - Battery DATE Code and MHOs input
OK
APPS
G
OK
H
APPS
I
ALARM LED (red)
FLASHING = Major Alarm
OFF = Minor Alarm
OFF = Operation Normal
<ESC>
OTHER
ESC
1/10
ESC
1000M
ESC
i